IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
123
Detector Status Display
AWACS™ Applications
The first field displays the point control. There are three designations that could appear in this field
The second field displays the point status. There are two designations that could appear in this field.
The device is a detector (an input device) so by referring to the descriptions below, it can be
determined that the point is in a normal state.
Inputs: (detectors, monitor modules, zones)
If the point is not in trouble or disabled, and the point is automatically controlled by the panel, the
display will be one of the following:
AUTOMATIC INACTIVE
AUTOMATIC ACTIVE
AUTOMATIC PREALARM
If the point is disabled, the display will be one of the following. The Trouble Status field will
appear if the point is in trouble.
DISABLED
INACTIVE
<Trouble Status>*
DISABLED
ACTIVE
<Trouble Status>*
DISABLED
PREALARM
<Trouble Status>*
If the point is in trouble, the display will read:
TROUBLE
INACTIVE
<Trouble Status>*
TROUBLE
A
CTIVE
<Trouble Status>*
TROUBLE
PREALARM
<Trouble Status>*
*The field
<
Trouble Status
>
will contain a device trouble message. Refer to this panel’s Operations
manual for information on these messages.
Line 7 - The custom label for this point
Line 8 - Continuation of the point’s custom label, first zone, and device type
Lines 9,10 - a display of all the zones that contain the current point being read.
Lines 11through 14 -These lines will have values in them only if the device is a detector. They will
not display for wireless detectors.
Line 11
VALUES
:
The screen displays the Alarm and Prealarm values that are in effect when read status is
requested. For example, if occupied settings are in effect, occupied values will display
Point Control
Designation
Description
AUTOMATIC
The point is being controlled automatically by the panel.
DISABLED
The point has been forced into a disabled state by an outside source.
TROUBLE
The point is in a trouble state and is no longer functioning automatically.
Point Status
Designation
Description
INACTIVE
The point is currently reporting no events.
ACTIVE
The point is currently in an off-normal status.
PREALARM
The point is currently in a prealarm status.
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...