IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
121
Detector Status Display
AWACS™ Applications
D.4.2 To Test Detectors Set Below 0.50% Obscuration per Foot
Using alarm sensitivities below 0.50% obscuration per foot requires a 90-day test to ensure that the
detector environment is suitable for the higher sensitivity setting. To meet Notifier and
Underwriters Laboratory requirements, test each detector planned to operate below 0.50%/ft
obscuration as follows:
1.
Set the detector as follows:
2.
Operate detectors continuously for 90 days with all environmental factors (such as,
temperature, humidity, air flow, occupancy, and so on) similar to the intended application for
the detectors. Record all events for each tested detector with an electronic History buffer or a
printout.
3.
At the end of the 90-day test: An authorized Notifier representative, or an end user trained by
an authorized Notifier representative must inspect the results of the test. If the test results show
no alarms or pre-alarms for the tested detectors, reprogram the fire alarm system to set the
Alarm sensitivity to the more sensitive Pre-Alarm level of the test.
D.5 Detector Status Display
D.5.1 Detector Maintenance Display
Should the panel detect a low chamber value or maintenance condition with a detector, it will
generate a point trouble as described in the operations manual for this panel. The following Read
Status screen displays detector information that applies to the state of the smoke detector. It can be
reached with the following commands, starting at the Main Menu screen:
Press
MAIN MENU
Press
READ STATUS
Press
READ STATUS POINT SELECT
(enter the detector point address)
Press
ACCEPT
Figure D.6 Smoke Detector Screen - Read Status
Step
Action
1
Initially set to the 0.50% obscuration per foot Alarm level.
2
Set the Pre-Alarm level to the desired final Alarm sensitivity.
3
Set the Pre-Alarm to Alert mode (non-latching).
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
R E A D A D D R E S S :
L 0 3 D 0 5 2
A U T O M A T I C
I N A C T I V E
E L E V A T O R L O B B Y
E A S T W I N G
F I F T H F L O O R
Z 0 0 3
S M O K E ( P H O T O )
Z 0 0 5 ,
Z 0 2 7 ,
Z 0 6 6 ,
,
,
,
,
,
,
,
V A L U E S : 0 1 1 % O F A L A R M , 0 4 5 % O F P R E A L A R M
A L A R M : 6 = 1 . 6 6 % , P R E A L A R M : 3 = 0 . 4 7 %
A C T I O N / S T A T U S : N O N E / V E R Y C L E A N
P E A K S : 5 6 % V E R I F Y C O U N T : 0 2 C O - O P : D 1 0 0 , 1 5 8
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
B A C K
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...