background image

SUBHEAD

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

-

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

Due to continuous improvement, JCI reserves the right to change product specifications without notice.

take advantage of the included wall box that 

may be installed during the rough-in phase. 

For retrofit applications not requiring electrical 

conduit termination, the unit may be installed 

using the retrofit mounting plate that simplifies 

the installation process. 

1. The CMS-1655 flush thin mount model 

should be mounted in a location that provides 

convenient access so the display may be 

viewed with minimal glare and the touch 

screen is easily accessible to facilitate 

silencing the unit in the event of an alarm 

condition. 

2. If this is a new construction project and the 

wall box has been installed, you may skip the 

next two steps. If this is a retrofit application 

and existing drywall is in place, then proceed 

with the next step to prepare the opening for 

the CMS-1655 flush thin mount model. 

3. Using the retrofit mounting plate (see 

Figure 2

) as a template, trace the inner outline 

onto the drywall at the desired mounting 

location with a pencil or marker. Also mark 

the location of the two mounting holes on 

the drywall. Cut along the traced outline 

with a drywall knife or saw, taking care not 

to make the opening too large. Drill out the 

two holes to clear access to the mounting 

clip nuts. Remove the cut section of drywall 

and discard. Be sure to brush off any drywall 

dust or remnants from the inside surface of 

the opening to ensure proper adhesion of the 

retrofit mounting plate. 

4. Remove the paper backing from the two 

adhesive strips on the retrofit mounting 

plate and insert it into the cut opening of the 

drywall. The retrofit plate should be oriented 

such that the corner notch is located at the 

lower left corner of the opening in the drywall, 

with the tabs bent towards you. Using the 

four tabs on the retrofit mounting plate as 

alignment guides, press the mounting plate 

onto the inside surface of the drywall opening 

firmly to ensure maximum adhesion.

5. The electrical connections must be 

terminated before installing the stainless 

steel faceplate of the CMS-1655. Run the 

4-conductor, dual twisted pair, electrical 

connection from the nearest FMS-1650/55 or 

HMS-1650/55. Refer to the wiring diagram 

shown on 

page 7

 for details. 

6. Terminate the interface cable originating 

from the host controller at the 4-position and 

3-position terminal blocks on the back side 

of the CMS-1655 display, ensuring proper 

electrical connections. Power connections 

should be terminated at +V and GND 

of the 4-position terminal block, and the 

subnet connections should be terminated 

at NETWK+ and NETWK- at the 3-position 

terminal block (see page 7). Do not apply 

power until the faceplate has been securely 

fastened to the wall.

 

7. With the electrical connections properly 

terminated, the stainless steel faceplate 

may be installed using the two flat head 

machine screws. For retrofit applications 

where the mounting plate has been affixed 

to the inside surface of the drywall, the two 

mounting screws thread into the clip nuts of 

the mounting plate. For those applications 

where the wall box has been installed, the two 

mounting screws fasten the faceplate directly. 

8. With power applied, the CMS-1655 should 

display the offline status of four stations at the 

default subnet addresses. 

 

Mounting Procedure: Surface Mount

The CMS-1655 surface mount model 

incorporates a low-profile display enclosure 

that may be mounted to any surface using 

wall anchors or the appropriate fastening 

hardware. For new construction applications, 

the CMS-1655 surface mount enclosure is 

designed to accommodate a standard single-

gang (2x4) wall box. This allows the wall box 

to be installed during the rough-in phase, 

and the appropriate electrical conduits to be 

installed as necessary. The CMS-1655 is 

configured at the factory to monitor up to four 

controllers. The user may change the factory-

default settings by following the procedures 

outlined in the 

Quick Start Guide

 (page 3) 

section of this manual. 

The electrical connections to the CMS-1655 

are made via convenient terminal block 

connectors as shown on

 page 7.

 

All wiring should conform to local regulations 

and to the National Electrical Code (NEC). 

Precautions must be taken to avoid running 

communications wiring in the same conduit as 

line voltage or other conductors that supply 

highly inductive loads such as generators, 

INSTALLATION MANUAL

Fig 2. Retrofit mounting plate

Содержание CMS-1655

Страница 1: ...ore beginning installation North American Emissions Compliance United States Canada Installation This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipmen...

Страница 2: ...655 to Nearest JCI Controller 7 Notes 8 PROGRAMMING MANUAL Introduction 9 Main Setup Menu 9 Unit Setup 10 Configuring Monitor Settings 10 Configuring Audible Alert Settings 11 System Setup 12 Configur...

Страница 3: ...5 or by separate power supply 18 to 32 Vdc Touchscreen User Interface LCDSizeandType 3 2 diagonal transmissive Resolution 240 pixels x 320 pixels portrait mode Viewing Area 50 60 mm x 66 80 mm Color D...

Страница 4: ...parameter is within defined normal operating limits Yellow indicates that the monitored parameter has drifted outside of the normal operating limits and is approaching the alarm region Red indicates t...

Страница 5: ...tainless steel faceplate of the CMS 1655 Run the 4 conductor dual twisted pair electrical connection from the nearest FMS 1650 55 or HMS 1650 55 Refer to the wiring diagram shown on page 7 for details...

Страница 6: ...wn on page 7 for details 6 Terminate the interface cable originating from the host controller at the 4 position and 3 position terminal blocks on the back side of the CMS 1655 display ensuring proper...

Страница 7: ...used to indicate that a door is open at a monitored FMS unit if a door switch has been incorporated with the FMS A red background with the red exclamation point action icon indicates that the monitor...

Страница 8: ...four parameters of up to four independent JCI controllers Once the individual controllers have been specified the parameters at each monitored controller may be selected This is accomplished by tappin...

Страница 9: ...tandard view is selected may be adjusted either by using the hotspots on the main display or by selecting Display Setup Set Time Date The CMS 1655 is also designed to request time and date settings pe...

Страница 10: ...N7 CN3 NETWK NETWK GND V FMS or HMS Backplane Connections Daisy chain together the SUB_NETs on the backplanes of all the FMS 1655 and or HMS 1655 units that will be monitored by the CMS 1655 Connect t...

Страница 11: ...improvement TRIATEK reserves the right to change product specifications without notice Due to continuous improvement JCI reserves the right to change product specifications without notice INSTALLATIO...

Страница 12: ...ed Menu screens time out after 90 seconds of inactivity while configuration screens automatically time out after 60 seconds This prevents unauthorized access to the user menu system should a unit be i...

Страница 13: ...e CMS 1655 Single Station Monitor should be selected if a single controller is being monitored If multiple parameters at a single station need to be monitored then the monitor mode should be specified...

Страница 14: ...lected After selecting the specific stations which should activate the audible alarm when the alarm status occurs pressing the Next button invokes the next configuration screen as shown in Figure 19 w...

Страница 15: ...e configuration settings associated with the CMS 1655 alarm facility may be accessed at the Alarms Setup menu shown in Figure 22 Options on this menu allow individual alarms to be enabled for each of...

Страница 16: ...missioned mode is selected at a monitored HMS 1650 55 These modes are indicated by an action icon represented as a red circle with a line through its center The Safety Halo status indicator if enabled...

Страница 17: ...ormal operating hours if Nightly Auto Dim is enabled or continuously otherwise To configure the Safety Halo feature to reduce in brightness intensity during evening hours or otherwise select the Night...

Страница 18: ...uld be entered as a two digit entry For convenience the time and date may also be entered directly from the main screen Single Station Monitor mode only by tapping the time and date fields respectivel...

Страница 19: ...een made to the network parameters subnetwork address Selecting this option invokes the warning message as shown in Figure 31 informing the user that the CMS 1655 will be reset when the OK button is t...

Страница 20: ...Due to continuous improvement JCI reserves the right to change product specifications without notice User Menu Flow Diagram 17 PROGRAMMING MANUAL...

Страница 21: ...The Next Generation in Critical Airflow Controls CMS 1655 Central Monitoring Station Installation and Programming Manual LB CMS1655 S LB CMS1655 T Code No LIT 12013121 Rev A Issued August 2018 Refer...

Отзывы: