11
-
If
Single Station Monitor
mode is chosen, then
the user is prompted to select the
Viewing
Mode
option:
Standard View
or
Status-only
View
.
Standard View
presents the usual
single sensor main display that is shown on
an FMS-1655 configured for single sensor
mode (or dual sensor, primary/secondary
view).
Status-only
View presents the view
shown below in
Figure 17
, with no numeric
values, and only background color to indicate
the units current status.
Tapping
Finish
at the
Monitor Setup
configuration screen stores that subnetwork
addresses of the controller to be monitored
and begins to poll each one individually.
Configuring Audible Alert Settings
The
Audible Alert
option on the
Unit Setup
menu provides support for configuring the
settings associated with the audible alarming
capabilities of the CMS-1655, and invokes the
configuration screen shown in
Figure 18
when
selected.
After selecting the specific stations which
should activate the audible alarm when
the alarm status occurs, pressing the Next
button invokes the next configuration screen
as shown in
Figure 19
where the user may
specify the operating mode for the alarm
buzzer,
Audible Mode
or
Silent Mode
.
Selecting
Audible Mode
allows the user to
specify a
Delay Time
in seconds or minutes,
which defines the period of time the audible
alarm activation will be delayed when alarm
status occurs.
Selecting
Audible Mode
on the
Alarm Buzzer
Settings
configuration screen also allows
an
Alarm Quiet Period
to be defined, during
which the audible alarm will be muted
whenever an alarm condition occurs at one of
the monitored stations or controllers.
Tapping the
Next
button invokes the
Alarm
Quiet Period
configuration screen as shown
in
Figure 20
. At this screen, the starting and
ending hour may be specified which defines
the alarm buzzer muted period.
PROGRAMMING MANUAL
Fig. 17 Status-only View
Fig. 18 Alarm Buzzer Settings
Fig. 19 Specifying Operating Modes
for the Alarm Buzzer Settings