background image

www.johnsonandstarley.co.uk

16

15.    SERVICING & MAINTENANCE

IMPORTANT:  Ensure  that  the  gas  and  electricity  supplies  are  isolated  before  commencing  any  servicing  & 
maintenance or replacement of components. Because the appliance is room sealed, it is also imperative that if 
at any stage of repairs the gasket on the sealing plate is damaged it MUST be replaced! After completion of any 
maintenance, always test for gas tightness and carry out a complete functional test of the appliance in accordance 
with the Commissioning Instructions at paragraphs  13.1 to 13.6 inclusive.

15.1    ROUTINE MAINTENANCE

15.1.1  Operate the appliance and check for the correct function of the burner and controls.
15.1.2  Turn OFF the gas and electrical supplies to the appliance.
15.1.3  Remove the air heater front panel.
15.1.4  Remove and check the return air filter/cleaner for cleanliness, remove and clean the Air Circulation 

fan as detailed in paragraph 15.8.

15.1.5  Remove the Burner and Controls Assembly as detailed in para 8.2. Inspect and clean the Main 

Burner and injector as necessary. Examine the Main Burner for cracks, including hairline cracks, 
exchanging the burner as necessary.

15.1.6  Inspect and clear the pilot burner orifice.
15.1.7  Clean the heat exchanger flueways by thoroughly brushing from above and below.
15.1.8  By viewing through the Fan Aperture, and using a torch or similar, examine the heat exchanger 

externally for signs of cracks or holes, particularly around welded joints.

15.1.9  Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper 

access port, and again examine the heat exchanger for signs of cracks or holes, particularly around 
welded joints, whilst again viewing through the Fan Aperture.

15.1.10  Refit the Air Circulation fan, Burner and Controls Assembly, and air filter/air cleaner. 
15.1.11  Light the appliance and note the main burner flame profile. If the flame profile is affected when 

the Air Circulation fan switches on, check for any air leaks between the air heater and the base 
plenum, paying particular attention to heaters with rear draught diverters. Rectify any air leaks before 
continuing with this procedure.

15.1.12  Allow the air heater to operate for approximately 15 minutes to ensure stability, and with the main 

burner lit, ensure that the operation of Air Circulation fan does not affect the main burner flame 
profile.

15.2 BURNER 

& CONTROL ASSEMBLY REMOVAL

15.2.1  Ensure that the Gas and Electrical supplies are switched OFF
15.2.2  Remove the appliance lower door.
15.2.3  Disconnect the igniter at the Piezo unit.
15.2.4  Disconnect the Multifunctional Control electrical connections.
15.2.5  Disconnect the gas supply by breaking the union at the input side of the Multifunctional Control.
15.2.6  Release the burner assembly fixing screw at the left hand side of the burner bar and withdraw the 

Burner and Controls Assembly

15.2.7  Refit the Burner and Controls  Assembly in reverse order.

15.3 

BURNER & CONTROLS ASSEMBLY CLEANING

15.3.1  Remove the Burner and Controls Assembly as detailed in 15.2.
15.3.2  Remove the 2 screws securing the gas feed pipe to the burner bar, and remove the burner bar.
15.3.3  Clean the burner thoroughly both inside and out with a soft brush. 

DO NOT ENLARGE, DISTORT 

OR DAMAGE BURNER HOLES.

15.3.4  Reassemble in reverse order.

15.4 

MAIN INJECTOR REMOVAL, CLEANING & REPLACEMENT

15.4.1  Remove the Burner and Controls Assembly as detailed in 15.2.
15.4.2  Unscrew the main injector from the housing.
15.4.3  Clean as necessary. 

DO NOT ENLARGE, DISTORT OR DAMAGE THE MAIN INJECTOR HOLE.

15.4.4  If the injector is to be replaced, ensure that it is correctly marked, referring to the data badge for 

details.

15.4.5  Refitment or replacement is in reverse order.

15.5 

PILOT BURNER, THERMOCOUPLE & ELECTRODE REMOVAL AND REPLACEMENT

15.5.1  Remove the Burner and Controls Assembly as detailed in 15.2
15.5.2  Disconnect the Igniter lead from the Electrode.
15.5.3  Release the Pilot Feed Pipe from the pilot injector.
15.5.4  Release the retaining nut and withdraw the Thermocouple from the Pilot Burner Assembly, taking 

care to avoid causing damage to the capillary.

15.5.5  Release the Electrode securing nut from the Pilot Burner Assembly and withdraw the Electrode.

Содержание 42-451-09

Страница 1: ...NSTALLATION COMMISSIONING SERVICING INSTRUCTIONS HI SPEC J40 Warm Air Heater with System E T Conventional Control Hi Spec J40 G C No 42 451 09 These instructions are to be left with the User Publicati...

Страница 2: ...ral Description 3 3 Building Standards Regulations 4 4 Safety Gas Information 4 General Safety Information Gas Categories Gas Supply 5 Technical Data 5 6 Heater Compartment Clearances 5 7 Ventilation...

Страница 3: ...nitoring Device TTB 15 Time Control 16 Thermista stat Thermostat 2 GENERAL DESCRIPTION 2 1 HI SPEC J40 is an open flued fan assisted downflow ducted warm air heater which may be supplied with SYSTEM E...

Страница 4: ...appliance is CE certificated for safety and performance It is important that no modifications are made to this appliance unless fully approved in writing by Johnson Starley Ltd If in doubt please rin...

Страница 5: ...rtition or a perforated metal partition with the perforations not exceeding 13mm The secondary flue must be a tight fit where it passes through the partition and must be suitably protected see BS 5440...

Страница 6: ...ain living area but from a convenient central area serving the remainder of the dwelling 8 1 2 The return air system should be constructed of fire resistant material The flue shall not be run through...

Страница 7: ...s 9 5 8 The flue should run as vertically as possible Horizontal runs should be avoided if at all possible and any directional change should be as gentle as possible If there is any doubt about the fl...

Страница 8: ...Below eaves 200mm F Below balconies 200mm G From a vertical drain pipe or soil pipe 150mm H From an internal or external corner Greater than 450mm protrusion 300mm I Above ground roof or balcony leve...

Страница 9: ...t and outlet resistance of the actual or proposed flue NOTE K and Sum K are obtained from Table 2 Ko and Ki are obtained from Table 5 c Table 2 gives resistance factors for common flue components for...

Страница 10: ...positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must be allowed for 9 5 14 Where flue blocks are used builders...

Страница 11: ...4 762881 TABLE 4 WORKED EXAMPLE OF EQUIVALENT FLUE HEIGHT Ridge Terminal 2 x 300mm Extensions 4 x 1000mm Extensions 45 Elbow 300mm Extension 45 Elbow 2 x 300mm Extensions Appliance Draught Diverter 4...

Страница 12: ...to vibration c Connect the thermista stat wires to terminals 7 and 8 on the terminal block see Figure 14 15 11 GAS See BS 5864 and BS 6891 11 1 The local gas supply conditions MUST be adequate for th...

Страница 13: ...e 9 13 3 3 Turn the heater Gas supply ON test for gas tightness and purge the whole gas pipe as described in BS 6891 13 3 4 Referring to Figure 9 press and hold the OPERATING CONTROL and whilst observ...

Страница 14: ...ing has been sized accordingly set the RATE SWITCH to MIN thus reducing the fan speed ii BASIC HEATER The fan speed is adjusted by selecting the fan speed at control panel decrease voltage selection t...

Страница 15: ...e delay before the Main Burner re ignites 14 USERS INSTRUCTIONS 14 1 If the building is unoccupied ensure that the user instructions are left taped to the air heater for the user s reference and that...

Страница 16: ...ir heater and the base plenum paying particular attention to heaters with rear draught diverters Rectify any air leaks before continuing with this procedure 15 1 12 Allow the air heater to operate for...

Страница 17: ...al supply is isolated 15 9 2 Remove the appliance upper and lower doors release the securing screw and hinge down the fan chamber door SYSTEM E T models 15 9 3 Disconnect the following a Air circulati...

Страница 18: ...lips and press the switch out of the fascia panel 15 12 10 Refitting or replacement is in reverse order WARNING The fascia panel is held in place by push fit retainers which must be removed with cauti...

Страница 19: ...y replacement arrangement invalid DEFECT DIAGNOSIS ITEM SYMPTOM POSSIBLE CAUSE REMEDY 1 Pilot will not light No gas supply to heater Check for gas at inlet pressure test point on Multifunctional Contr...

Страница 20: ...Main burner lights but fan fails to run after approximately 3 min Loose electrical connection at fan control Check connections Fan Delay Control faulty Replace Faulty fan assembly Replace taking care...

Страница 21: ...21 Sales Spares Replacement Help Line 01604 762881 FIGURE 11 HI SPEC J40 DIMENSIONS 17 DIMENSIONS...

Страница 22: ...ULT FINDING FLOWCHARTS MAIN BURNER NOT CYCLING ROOM TEMPERATURE TOO HIGH FAN CONTINUES TO RUN OR CYCLES AFTER HEATING IS TURNED OFF FAN OPERATES BUT BURNER CYCLES BEFORE REQUIRED TEMPERATURE IS REACHE...

Страница 23: ...23 Sales Spares Replacement Help Line 01604 762881 MAIN BURNER NOT OPERATING...

Страница 24: ...www johnsonandstarley co uk 24 20 DEFECT DIAGNOSIS FLOWCHART FIGURE 12 SYSTEM E T FUNCTIONAL DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 FIGURE 13 BASIC FUNCTIONAL DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 FIGURE 14 SYSTEM E T CONTROL CIRCUIT DIAGRAM 21 LOGIC DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 FIGURE 15 BASIC CONTROL CIRCUIT DIAGRAM...

Страница 28: ...in Injector Bray 23 1050 1 19 395 945 1000 0700570 Piezo Unit High Energy 1 20 245 509 1000 0513820 Fuse T3 15A anti surge 1 21 A432 0182000 Filter Tray 1 22 364 835 S00832 Solenoid Valve 1 23 A4300 0...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 FIGURE 16 HI SPEC J40 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...

Страница 30: ...m start control Heating zone control Fitted Not required WARM AIR HEATER Has the system been balanced in accordance with the heater manufacture s instructions Yes No Was an anemometer used Yes No Yes...

Страница 31: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 32: ...nson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2...

Отзывы: