Johnson & Starley 42-451-09 Скачать руководство пользователя страница 5

5

Sales/Spares & Replacement Help Line 01604 762881

GAS LEAKS

DO NOT OPERATE ANY ELECTRICAL SWITCHES, OR USE A 

NAKED FLAME TURN OFF THE GAS SUPPLY. VENTILATE THE 

AREA BY OPENING DOORS AND WINDOWS.

CALL THE NATIONAL GAS 

EMERGENCY SERVICE ON

0800 111999

6. 

HEATER COMPARTMENT CLEARANCES 

(see BS 5864)

6.1 

IMPORTANT:   If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that 
installation is carried out such that the rear left hand corner of the heater is aligned with the rear left hand 
corner of the base duct, so that any overhang or blanking off will be at the front and/or right hand side. In 
any event, blanking plates must be mechanically secured and all joints sealed.

6.2 

When the heater is fitted into a compartment consideration should be given to the space required for the 
removal and replacement of the filter tray and the entry of the gas and electrical supplies.

6.3 

For service access, a minimum of 500mm (20”) is required at the front of the heater. Space must also be 
allowed, in a compartment installation, to permit the removal of the heater. The clearance between the 
appliance and the compartment should  be not less than 75mm (3”). However, if clearances are less than 
75mm, the  internal surface of the compartment must be lined with non-combustible material. The compartment 
must be of a fixed rigid structure.

6.4 

In airing cupboard installations, the part used as the air heater compartment must comply with the relevant 
section of BS 5864 and must be completely separated by either a non-combustible partition or a perforated 
metal partition with the perforations not exceeding 13mm (½”). The secondary flue must be a tight fit where 
it passes through the partition and must be suitably protected (see BS 5440:Part 1).

6.5 

In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided 
that in addition, all internal surfaces, including the base, are non-combustible or lined with non-combustible 
material. This requirement is applicable only to dwellings of more than two storeys. Combustible floors must 
be insulated from the heater.

6.6 

In free-standing installations, (see instructions packed with free standing kit), only one or two walls will be in 
contact with the air heater and therefore complying with the relevant section of BS 5864.

6.7 

If the Air Heater is to be installed onto a combustible surface, a suitable base tray (BT40) is required. However, 
when a base duct is used, this provides sufficient insulation, and no insulation is required.

6.8 

For Slot Fix applications (see instructions packed with the Slot Fix Kit), it is important to ensure that the draught 
diverter relief is maintained on both sides of the application.

5. 

TECHNICAL DATA

TABLE 1

HI-SPEC J40

GAS

G20

GAS SUPPLY PRESSURE

20mbar

GAS CATEGORY

I 2 H

COUNTRIES OF INSTALLATION

GB & IE

ELECTRICAL SUPPLY

230v ~ 50Hz fused 5A (150 watts)

AIR HEATER

LOW RATE

MEDIUM  RATE

HIGH RATE

KW

MJ/h

Btu/h

KW

MJ/h

KW

KW

MJ/h

Btu/h

INPUT (GROSS)

11.75

42.35

40,100

13.5

48.58

46,050

15.18

54.65

51,800

OUTPUT

8.79

31.65

30,000

10.26

36.92

32,000

11.72

42.2

40,000

GAS RATE CV 1037Btu/FT³

1.08m

3

/h (38.4ft

3

/h)

1.24m

3

/h (44.1ft

3

/h)

1.40m

3

/h (49.8ft

3

/h)

BURNER SETTING PRESSURE (HOT)

9.2mbar (3.7 in wg)

12.2mbar (4.9 in wg)

16.0mbar (6.4 in wg)

MAIN INJECTOR

BRAY CAT 23/1050 

Содержание 42-451-09

Страница 1: ...NSTALLATION COMMISSIONING SERVICING INSTRUCTIONS HI SPEC J40 Warm Air Heater with System E T Conventional Control Hi Spec J40 G C No 42 451 09 These instructions are to be left with the User Publicati...

Страница 2: ...ral Description 3 3 Building Standards Regulations 4 4 Safety Gas Information 4 General Safety Information Gas Categories Gas Supply 5 Technical Data 5 6 Heater Compartment Clearances 5 7 Ventilation...

Страница 3: ...nitoring Device TTB 15 Time Control 16 Thermista stat Thermostat 2 GENERAL DESCRIPTION 2 1 HI SPEC J40 is an open flued fan assisted downflow ducted warm air heater which may be supplied with SYSTEM E...

Страница 4: ...appliance is CE certificated for safety and performance It is important that no modifications are made to this appliance unless fully approved in writing by Johnson Starley Ltd If in doubt please rin...

Страница 5: ...rtition or a perforated metal partition with the perforations not exceeding 13mm The secondary flue must be a tight fit where it passes through the partition and must be suitably protected see BS 5440...

Страница 6: ...ain living area but from a convenient central area serving the remainder of the dwelling 8 1 2 The return air system should be constructed of fire resistant material The flue shall not be run through...

Страница 7: ...s 9 5 8 The flue should run as vertically as possible Horizontal runs should be avoided if at all possible and any directional change should be as gentle as possible If there is any doubt about the fl...

Страница 8: ...Below eaves 200mm F Below balconies 200mm G From a vertical drain pipe or soil pipe 150mm H From an internal or external corner Greater than 450mm protrusion 300mm I Above ground roof or balcony leve...

Страница 9: ...t and outlet resistance of the actual or proposed flue NOTE K and Sum K are obtained from Table 2 Ko and Ki are obtained from Table 5 c Table 2 gives resistance factors for common flue components for...

Страница 10: ...positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must be allowed for 9 5 14 Where flue blocks are used builders...

Страница 11: ...4 762881 TABLE 4 WORKED EXAMPLE OF EQUIVALENT FLUE HEIGHT Ridge Terminal 2 x 300mm Extensions 4 x 1000mm Extensions 45 Elbow 300mm Extension 45 Elbow 2 x 300mm Extensions Appliance Draught Diverter 4...

Страница 12: ...to vibration c Connect the thermista stat wires to terminals 7 and 8 on the terminal block see Figure 14 15 11 GAS See BS 5864 and BS 6891 11 1 The local gas supply conditions MUST be adequate for th...

Страница 13: ...e 9 13 3 3 Turn the heater Gas supply ON test for gas tightness and purge the whole gas pipe as described in BS 6891 13 3 4 Referring to Figure 9 press and hold the OPERATING CONTROL and whilst observ...

Страница 14: ...ing has been sized accordingly set the RATE SWITCH to MIN thus reducing the fan speed ii BASIC HEATER The fan speed is adjusted by selecting the fan speed at control panel decrease voltage selection t...

Страница 15: ...e delay before the Main Burner re ignites 14 USERS INSTRUCTIONS 14 1 If the building is unoccupied ensure that the user instructions are left taped to the air heater for the user s reference and that...

Страница 16: ...ir heater and the base plenum paying particular attention to heaters with rear draught diverters Rectify any air leaks before continuing with this procedure 15 1 12 Allow the air heater to operate for...

Страница 17: ...al supply is isolated 15 9 2 Remove the appliance upper and lower doors release the securing screw and hinge down the fan chamber door SYSTEM E T models 15 9 3 Disconnect the following a Air circulati...

Страница 18: ...lips and press the switch out of the fascia panel 15 12 10 Refitting or replacement is in reverse order WARNING The fascia panel is held in place by push fit retainers which must be removed with cauti...

Страница 19: ...y replacement arrangement invalid DEFECT DIAGNOSIS ITEM SYMPTOM POSSIBLE CAUSE REMEDY 1 Pilot will not light No gas supply to heater Check for gas at inlet pressure test point on Multifunctional Contr...

Страница 20: ...Main burner lights but fan fails to run after approximately 3 min Loose electrical connection at fan control Check connections Fan Delay Control faulty Replace Faulty fan assembly Replace taking care...

Страница 21: ...21 Sales Spares Replacement Help Line 01604 762881 FIGURE 11 HI SPEC J40 DIMENSIONS 17 DIMENSIONS...

Страница 22: ...ULT FINDING FLOWCHARTS MAIN BURNER NOT CYCLING ROOM TEMPERATURE TOO HIGH FAN CONTINUES TO RUN OR CYCLES AFTER HEATING IS TURNED OFF FAN OPERATES BUT BURNER CYCLES BEFORE REQUIRED TEMPERATURE IS REACHE...

Страница 23: ...23 Sales Spares Replacement Help Line 01604 762881 MAIN BURNER NOT OPERATING...

Страница 24: ...www johnsonandstarley co uk 24 20 DEFECT DIAGNOSIS FLOWCHART FIGURE 12 SYSTEM E T FUNCTIONAL DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 FIGURE 13 BASIC FUNCTIONAL DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 FIGURE 14 SYSTEM E T CONTROL CIRCUIT DIAGRAM 21 LOGIC DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 FIGURE 15 BASIC CONTROL CIRCUIT DIAGRAM...

Страница 28: ...in Injector Bray 23 1050 1 19 395 945 1000 0700570 Piezo Unit High Energy 1 20 245 509 1000 0513820 Fuse T3 15A anti surge 1 21 A432 0182000 Filter Tray 1 22 364 835 S00832 Solenoid Valve 1 23 A4300 0...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 FIGURE 16 HI SPEC J40 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...

Страница 30: ...m start control Heating zone control Fitted Not required WARM AIR HEATER Has the system been balanced in accordance with the heater manufacture s instructions Yes No Was an anemometer used Yes No Yes...

Страница 31: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 32: ...nson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2...

Отзывы: