Johnson & Starley 42-451-09 Скачать руководство пользователя страница 13

13

Sales/Spares & Replacement Help Line 01604 762881

FIGURE 6. FAN PERFORMANCE GRAPH

13.  COMMISSIONING

13.1 

PREPARATION

 

After installation of the appliance, you MUST do the following:
13.1.1  Test for gas leakage using proprietary detection fluid and seal any leaks found.
13.1.2  Carry out preliminary electrical system checks.
13.1.3  Ensure that:

a.   filter, fan and fan compartments are free from obstructions.
b.   all registers or grilles are open and conform to design specifications.
c.   return, relief and ventilation air installations are adequate.

13.2 

SYSTEM BALANCING

13.2.1   Set the air heater electrical supply 

ON

.

13.2.2   Set the thermista-stat to the “SUMMER AIRFLOW” position ‘

I

’.

13.2.3   Balance the system to provide the required volume proportions at the warm 

air outlets.

NOTE: 

  If the system includes ceiling diffusers, 

the air through these should be NOT LESS 
THAN 1.5m/s (300ft/min), except for very 
small rooms, (i.e. bathrooms etc.). Outlet 
faces may require partial blanking in order 
to achieve this.

13.2.4  Set the SUMMER AIRFLOW switch to ‘

0

’.

13.3    LIGHTING IGNITION & MAIN BURNER

 WARNING: 

 If the pilot light is extinguished either 

intentionally or unintentionally, no attempt should be 
made to relight the gas for a minimum of 3 minutes. 
Ensure Electrical supply, time control and Selector 
switches  are set to ‘

OFF

’.

13.3.1  Set the Thermista-stat/room thermostat to 

its lowest or 

OFF

 setting.

13.3.2  On the Multifunctional Control, remove the 

Outlet Pressure test point cover, and fit a 
pressure test gauge, refer Figure 9.

13.3.3  Turn the heater Gas supply 

ON

, test for gas tightness and purge the whole gas pipe as described 

in BS 6891.

13.3.4  Referring to Figure 9, press and hold the OPERATING CONTROL, and whilst observing the Pilot 

Burner, repeatedly press the Piezo igniter button until the Pilot Burner ignites.

13.3.5  After 20 seconds release the Multifunctional Control OPERATING CONTROL and let it spring out; 

ensure that the Pilot Burner remains alight. If the Pilot Burner extinguishes, rotate the  OPERATING 
CONTROL clockwise to the ‘

’ position and ensure that the OPERATING CONTROL is fully reset. Wait 

three minutes and repeat steps 13.3.4 and 13.3.5, holding the OPERATING CONTROL depressed 
for a longer period, until the Pilot burner remains alight.

13.3.6   With the Pilot Burner lit, depress the OPERATING CONTROL and turn it to the position indicated by 

the flame symbol.

13.3.7  Ensure that the pilot flame envelops the thermocouple 

tip, see Figure 7.

13.3.8  Set the Heater Electricity supply 

ON

.

13.3.9  Set the Time Control to the required Heating On periods.
13.3.10  Set the Selector switch to ‘TIMED’.
13.3.11  Set the Thermista-stat or room thermostat to MAXIMUM.
13.3.12  Ensure that the Main Burner has now ignited.
13.3.13  Test for gas leakage at the supply, Multifunctional 

Control, Pilot and Main Burners using proprietary 
detection fluid, sealing any leaks found.

13.3.14  Allow the heater to operate for a minimum of 15 minutes 

to ensure stability.

FIGURE 5.  

ELECTRICAL DOOR ASSEMBLY

FIGURE 7.  ELECTRICAL DOOR ASSEMBLY

PILOT 

BURNER

THERMOCOUPLE

ELECTRODE

 

mbar     in.wg

 

0.50      0.20

 

0.375    0.15

 

0.25   0.10

 

0.125 0.05

  300  

400  

500  

600 

 700  

800ft³/min

  0.14  

0.19  

0.24  

0.28  

0.133  

0.08m³/sec

                                                       

 AIR VOLUME 

RESIST

ANCE EXTERNAL TO HEA

TER

Содержание 42-451-09

Страница 1: ...NSTALLATION COMMISSIONING SERVICING INSTRUCTIONS HI SPEC J40 Warm Air Heater with System E T Conventional Control Hi Spec J40 G C No 42 451 09 These instructions are to be left with the User Publicati...

Страница 2: ...ral Description 3 3 Building Standards Regulations 4 4 Safety Gas Information 4 General Safety Information Gas Categories Gas Supply 5 Technical Data 5 6 Heater Compartment Clearances 5 7 Ventilation...

Страница 3: ...nitoring Device TTB 15 Time Control 16 Thermista stat Thermostat 2 GENERAL DESCRIPTION 2 1 HI SPEC J40 is an open flued fan assisted downflow ducted warm air heater which may be supplied with SYSTEM E...

Страница 4: ...appliance is CE certificated for safety and performance It is important that no modifications are made to this appliance unless fully approved in writing by Johnson Starley Ltd If in doubt please rin...

Страница 5: ...rtition or a perforated metal partition with the perforations not exceeding 13mm The secondary flue must be a tight fit where it passes through the partition and must be suitably protected see BS 5440...

Страница 6: ...ain living area but from a convenient central area serving the remainder of the dwelling 8 1 2 The return air system should be constructed of fire resistant material The flue shall not be run through...

Страница 7: ...s 9 5 8 The flue should run as vertically as possible Horizontal runs should be avoided if at all possible and any directional change should be as gentle as possible If there is any doubt about the fl...

Страница 8: ...Below eaves 200mm F Below balconies 200mm G From a vertical drain pipe or soil pipe 150mm H From an internal or external corner Greater than 450mm protrusion 300mm I Above ground roof or balcony leve...

Страница 9: ...t and outlet resistance of the actual or proposed flue NOTE K and Sum K are obtained from Table 2 Ko and Ki are obtained from Table 5 c Table 2 gives resistance factors for common flue components for...

Страница 10: ...positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must be allowed for 9 5 14 Where flue blocks are used builders...

Страница 11: ...4 762881 TABLE 4 WORKED EXAMPLE OF EQUIVALENT FLUE HEIGHT Ridge Terminal 2 x 300mm Extensions 4 x 1000mm Extensions 45 Elbow 300mm Extension 45 Elbow 2 x 300mm Extensions Appliance Draught Diverter 4...

Страница 12: ...to vibration c Connect the thermista stat wires to terminals 7 and 8 on the terminal block see Figure 14 15 11 GAS See BS 5864 and BS 6891 11 1 The local gas supply conditions MUST be adequate for th...

Страница 13: ...e 9 13 3 3 Turn the heater Gas supply ON test for gas tightness and purge the whole gas pipe as described in BS 6891 13 3 4 Referring to Figure 9 press and hold the OPERATING CONTROL and whilst observ...

Страница 14: ...ing has been sized accordingly set the RATE SWITCH to MIN thus reducing the fan speed ii BASIC HEATER The fan speed is adjusted by selecting the fan speed at control panel decrease voltage selection t...

Страница 15: ...e delay before the Main Burner re ignites 14 USERS INSTRUCTIONS 14 1 If the building is unoccupied ensure that the user instructions are left taped to the air heater for the user s reference and that...

Страница 16: ...ir heater and the base plenum paying particular attention to heaters with rear draught diverters Rectify any air leaks before continuing with this procedure 15 1 12 Allow the air heater to operate for...

Страница 17: ...al supply is isolated 15 9 2 Remove the appliance upper and lower doors release the securing screw and hinge down the fan chamber door SYSTEM E T models 15 9 3 Disconnect the following a Air circulati...

Страница 18: ...lips and press the switch out of the fascia panel 15 12 10 Refitting or replacement is in reverse order WARNING The fascia panel is held in place by push fit retainers which must be removed with cauti...

Страница 19: ...y replacement arrangement invalid DEFECT DIAGNOSIS ITEM SYMPTOM POSSIBLE CAUSE REMEDY 1 Pilot will not light No gas supply to heater Check for gas at inlet pressure test point on Multifunctional Contr...

Страница 20: ...Main burner lights but fan fails to run after approximately 3 min Loose electrical connection at fan control Check connections Fan Delay Control faulty Replace Faulty fan assembly Replace taking care...

Страница 21: ...21 Sales Spares Replacement Help Line 01604 762881 FIGURE 11 HI SPEC J40 DIMENSIONS 17 DIMENSIONS...

Страница 22: ...ULT FINDING FLOWCHARTS MAIN BURNER NOT CYCLING ROOM TEMPERATURE TOO HIGH FAN CONTINUES TO RUN OR CYCLES AFTER HEATING IS TURNED OFF FAN OPERATES BUT BURNER CYCLES BEFORE REQUIRED TEMPERATURE IS REACHE...

Страница 23: ...23 Sales Spares Replacement Help Line 01604 762881 MAIN BURNER NOT OPERATING...

Страница 24: ...www johnsonandstarley co uk 24 20 DEFECT DIAGNOSIS FLOWCHART FIGURE 12 SYSTEM E T FUNCTIONAL DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 FIGURE 13 BASIC FUNCTIONAL DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 FIGURE 14 SYSTEM E T CONTROL CIRCUIT DIAGRAM 21 LOGIC DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 FIGURE 15 BASIC CONTROL CIRCUIT DIAGRAM...

Страница 28: ...in Injector Bray 23 1050 1 19 395 945 1000 0700570 Piezo Unit High Energy 1 20 245 509 1000 0513820 Fuse T3 15A anti surge 1 21 A432 0182000 Filter Tray 1 22 364 835 S00832 Solenoid Valve 1 23 A4300 0...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 FIGURE 16 HI SPEC J40 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...

Страница 30: ...m start control Heating zone control Fitted Not required WARM AIR HEATER Has the system been balanced in accordance with the heater manufacture s instructions Yes No Was an anemometer used Yes No Yes...

Страница 31: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 32: ...nson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2...

Отзывы: