background image

www.johnsonandstarley.co.uk

6

7. 

VENTILATION & COMBUSTION AIR

37.1 

The room or internal space in which the heater is installed requires a permanent air vent of minimum effec-
tive area 62cm

(9in

2

). The air vent should be either direct to outside air or to an adjacent room or internal 

space (other than a toilet or bathroom) that itself has an equivalent air vent direct to outside. 
Note: The above minimum area assumes that an ELJAN 6 circulator is fitted. 

7.2 

Combustion air may be introduced, via a 127mm (5”) nominal bore pipe, connected to a return air duct 
or plenum from a ventilated area and fitted with a lockable damper. The damper should be adjusted to 
control combustion airflow to 0.0108m

3

/s (22.9cfm), (i.e. 0.95m/s [165ft/min] velocity in a 127mm [5”] bore 

pipe). If this arrangement is used, a non-closeable warm air register MUST be provided in the same area 
as the front of the air heater or heater compartment if a return air grille is not located in that area.

7.3 

When installed in a compartment, two permanent ventilation openings into the compartment are required, 
one at high level and one at low level, both communicating either directly with outside air or with a venti-
lated room or space. The minimum effective areas specified in Table 1 are related to the rated heat input 
of the Air Heater, and assuming that and ELJAN 6 circulator is fitted.

7.4 

If any room or area from which air is drawn for ventilation or combustion contains an extract fan, the per-
manent vents must be sized to ensure that the operation of the appliance(s) at full rate is/are not adversely 
affected. A spillage test as specified in Safety Checks, paragraph 13.8 (is carried out and any remedial work 
undertaken.

8. 

DUCT SYSTEM

 (See British Design Manual - Gas fired Warm Air Heating)

8.1 

RETURN AIR

8.1.1 

Room-sealed appliances may be installed without return air ducting, provided that the path between 
the return air grille and the appliance return air inlet is protected in such a manner that the required 
air-flow will be maintained at all times. The return air grille MUST have a free area of not less than 
1593cm

 (291in

2

). It is recommended that the return air duct not be routed directly from the main 

living area, but from a convenient central area serving the remainder of the dwelling.

8.1.2  

The return air system should be constructed of fire-resistant material. The flue shall not be run through 
an area serving as a return air plenum. It is extremely important that the correct size of return air 
grilles and ducting is used. For heaters on maximum output the return air duct size should not be 
less than the equivalent of 300mm x 300mm (12” x 12”). If flexible duct is used the duct diameter 
should not be less than 350mm (16”) dia. The return air grille should have a free area of not less 
than 1593cm

2

 (291in

2

).

8.1.3  

An adequate and unobstructed return air path is essential from areas not served by a directly ducted 
return and to which warm air is delivered. All such rooms should be fitted with relief grilles which 
have a free area of 0.0088m

2

/kW (1in

2

/250Btu/h) of heat supplied to the room. The only exceptions 

are kitchens, bathrooms and WCs.

8.1.4  

The return air duct should allow for ease of removal for access to the flue.

8.1.5  

All duct work in the room or internal space in which the heater is installed shall be mechanically 
secured and sealed with ducting tape.

8.2 

WARM DELIVERED AIR

8.2.1 

All duct work, including riser ducts, should be fully insulated with 50mm (2”) fibreglass or similar. 
If short extended duct runs are taken below floor level these should be similarly insulated, and in 
addition wrapped with a sound vapour proof barrier, and protected from crushing.

8.2.2 

The duct system should be carefully designed (as given in the guidelines in the British System Design 
Manual) to suit the needs of its specific heating requirements and building layout. The type of duct 
system, (i.e. radial/extended plenum/stepped) should be installed using the least number of fittings 
to minimise airflow resistance. The base duct, which equalises the air pressure to supply ducts, 
shall be constructed to support the weight of the heater, which shall be secured to the plenum with 
screws on at least two sides, and sealed using self-adhesive foam strip, ducting tape or sealing 
compound. All ducting and blanking plates shall be mechanically secured and sealed.

TABLE 2. MINIMUM EFFECTIVE AREAS

VENTILATED FROM INSIDE 

BUILDING

Low level grille 352cm

2

 (54in

2

)

High level grille 176cm

2

 (27in

2

)

VENTILATED FROM OUTSIDE 

BUILDING

Low level grille 176cm

2

 (27in

2

)

High level grille 88cm

2

 (13in

2

)  

Содержание 42-451-09

Страница 1: ...NSTALLATION COMMISSIONING SERVICING INSTRUCTIONS HI SPEC J40 Warm Air Heater with System E T Conventional Control Hi Spec J40 G C No 42 451 09 These instructions are to be left with the User Publicati...

Страница 2: ...ral Description 3 3 Building Standards Regulations 4 4 Safety Gas Information 4 General Safety Information Gas Categories Gas Supply 5 Technical Data 5 6 Heater Compartment Clearances 5 7 Ventilation...

Страница 3: ...nitoring Device TTB 15 Time Control 16 Thermista stat Thermostat 2 GENERAL DESCRIPTION 2 1 HI SPEC J40 is an open flued fan assisted downflow ducted warm air heater which may be supplied with SYSTEM E...

Страница 4: ...appliance is CE certificated for safety and performance It is important that no modifications are made to this appliance unless fully approved in writing by Johnson Starley Ltd If in doubt please rin...

Страница 5: ...rtition or a perforated metal partition with the perforations not exceeding 13mm The secondary flue must be a tight fit where it passes through the partition and must be suitably protected see BS 5440...

Страница 6: ...ain living area but from a convenient central area serving the remainder of the dwelling 8 1 2 The return air system should be constructed of fire resistant material The flue shall not be run through...

Страница 7: ...s 9 5 8 The flue should run as vertically as possible Horizontal runs should be avoided if at all possible and any directional change should be as gentle as possible If there is any doubt about the fl...

Страница 8: ...Below eaves 200mm F Below balconies 200mm G From a vertical drain pipe or soil pipe 150mm H From an internal or external corner Greater than 450mm protrusion 300mm I Above ground roof or balcony leve...

Страница 9: ...t and outlet resistance of the actual or proposed flue NOTE K and Sum K are obtained from Table 2 Ko and Ki are obtained from Table 5 c Table 2 gives resistance factors for common flue components for...

Страница 10: ...positioned in a free air space where it is not shielded by any structure A minimum of 1m 3ft from any vertical or inclined roof structure must be allowed for 9 5 14 Where flue blocks are used builders...

Страница 11: ...4 762881 TABLE 4 WORKED EXAMPLE OF EQUIVALENT FLUE HEIGHT Ridge Terminal 2 x 300mm Extensions 4 x 1000mm Extensions 45 Elbow 300mm Extension 45 Elbow 2 x 300mm Extensions Appliance Draught Diverter 4...

Страница 12: ...to vibration c Connect the thermista stat wires to terminals 7 and 8 on the terminal block see Figure 14 15 11 GAS See BS 5864 and BS 6891 11 1 The local gas supply conditions MUST be adequate for th...

Страница 13: ...e 9 13 3 3 Turn the heater Gas supply ON test for gas tightness and purge the whole gas pipe as described in BS 6891 13 3 4 Referring to Figure 9 press and hold the OPERATING CONTROL and whilst observ...

Страница 14: ...ing has been sized accordingly set the RATE SWITCH to MIN thus reducing the fan speed ii BASIC HEATER The fan speed is adjusted by selecting the fan speed at control panel decrease voltage selection t...

Страница 15: ...e delay before the Main Burner re ignites 14 USERS INSTRUCTIONS 14 1 If the building is unoccupied ensure that the user instructions are left taped to the air heater for the user s reference and that...

Страница 16: ...ir heater and the base plenum paying particular attention to heaters with rear draught diverters Rectify any air leaks before continuing with this procedure 15 1 12 Allow the air heater to operate for...

Страница 17: ...al supply is isolated 15 9 2 Remove the appliance upper and lower doors release the securing screw and hinge down the fan chamber door SYSTEM E T models 15 9 3 Disconnect the following a Air circulati...

Страница 18: ...lips and press the switch out of the fascia panel 15 12 10 Refitting or replacement is in reverse order WARNING The fascia panel is held in place by push fit retainers which must be removed with cauti...

Страница 19: ...y replacement arrangement invalid DEFECT DIAGNOSIS ITEM SYMPTOM POSSIBLE CAUSE REMEDY 1 Pilot will not light No gas supply to heater Check for gas at inlet pressure test point on Multifunctional Contr...

Страница 20: ...Main burner lights but fan fails to run after approximately 3 min Loose electrical connection at fan control Check connections Fan Delay Control faulty Replace Faulty fan assembly Replace taking care...

Страница 21: ...21 Sales Spares Replacement Help Line 01604 762881 FIGURE 11 HI SPEC J40 DIMENSIONS 17 DIMENSIONS...

Страница 22: ...ULT FINDING FLOWCHARTS MAIN BURNER NOT CYCLING ROOM TEMPERATURE TOO HIGH FAN CONTINUES TO RUN OR CYCLES AFTER HEATING IS TURNED OFF FAN OPERATES BUT BURNER CYCLES BEFORE REQUIRED TEMPERATURE IS REACHE...

Страница 23: ...23 Sales Spares Replacement Help Line 01604 762881 MAIN BURNER NOT OPERATING...

Страница 24: ...www johnsonandstarley co uk 24 20 DEFECT DIAGNOSIS FLOWCHART FIGURE 12 SYSTEM E T FUNCTIONAL DIAGRAM...

Страница 25: ...25 Sales Spares Replacement Help Line 01604 762881 FIGURE 13 BASIC FUNCTIONAL DIAGRAM...

Страница 26: ...www johnsonandstarley co uk 26 FIGURE 14 SYSTEM E T CONTROL CIRCUIT DIAGRAM 21 LOGIC DIAGRAM...

Страница 27: ...27 Sales Spares Replacement Help Line 01604 762881 FIGURE 15 BASIC CONTROL CIRCUIT DIAGRAM...

Страница 28: ...in Injector Bray 23 1050 1 19 395 945 1000 0700570 Piezo Unit High Energy 1 20 245 509 1000 0513820 Fuse T3 15A anti surge 1 21 A432 0182000 Filter Tray 1 22 364 835 S00832 Solenoid Valve 1 23 A4300 0...

Страница 29: ...29 Sales Spares Replacement Help Line 01604 762881 FIGURE 16 HI SPEC J40 EXPLODED DIAGRAM 23 EXPLODED DIAGRAM...

Страница 30: ...m start control Heating zone control Fitted Not required WARM AIR HEATER Has the system been balanced in accordance with the heater manufacture s instructions Yes No Was an anemometer used Yes No Yes...

Страница 31: ...Company name Telephone No Gas safe register No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 06 Date Engineer name Company name Telephone No Gas...

Страница 32: ...nson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 Anniversary 1922 2...

Отзывы: