33
Figure6-8 the installation figure of Sensor A
If you selected water level sensor B, then water sensor installation method is
shown below:
connect green cable
connect black cable
connect green cable
connect white cable
Water level sensor
connector
A:the Installation location of
overflow water level
sensor.
1. B:the Installation
location of pump dryed
water level sensor.
2. C:Pump outlet.
3. S about 1-3 m .
For dry protection, the end with cable
of sensor should be upwards
For over-
flow protection, the end with cable of
sensor should be downwards.
Figure6-9 the installation figure of Sensor B