58
8.3.2.3 DSP parameter setting
Set the key parameters of inverter
Table 8-10 DSP parameter setting
Para Set
description
remark
Imotor
The overload current protection value of the
motor is generally set as 1.2 times the rated
current of the motor.
D-Power
Dry protection power, which shall be reset when the
load power rating is lower than Solar pumping
inverter. Recommended value is 30% of the rated
output power of Inverter. For example, the D-Power
of 1.1kW pump is 330.
D-Time
Dry out recovery tim:
auto dry out mode, after the warning of dry out and
inverter shut down, the duration from shut down to
restart. Default value is 30. Default duration is 30
minutes.
Detecting dry mode:after the warning of dry out and
inverter shut down, the duration from shut down to
restart. Default value is 30. Default duration is 30
minutes.
StopFreq
Stop frequency (Hz). Setting principle is stop
frequency when minimum flow is output.
F-Limit
Frequency limit, the maximum frequency that the
inverter can output.