69
State 110
Inverter shutdown.
When malfunction
disappear,
inverter can restart
automatic.
Array output low.
Usually appears in early
morning,
dusk
and cloudy
days. This situation is aim to
protect the motor of pump
and lengthen the lifetime.
State 114
Inverter shut down
until the water level
recover
or
protection recover
time is up, the
machine will restart
automatically.
Water level in
container higher
than
high-end
level sensor.
If this situation appears more
than once, please check
onsite and set the water level
sensor at a proper height.
Table9-2 Malfunction and troubleshooting
Condition
code
Phenomena
Cause value
Troubleshooting
Fault100
Inverter shutdown
and
will
restart
automatically after
the
fault
disappears
Short circuit in
output wire
Please check if there is short
circuit in output wires
Fault105
Inverter shutdown
and
will
restart
automatically after
the
fault
Load higher than
rated
output
power of inverter.
1. Please make sure the
system is proper designed.
The power of pump motor
should not be larger than