1.3 Instructions on EMI
JetWeb
Important!
Measures for increasing immunity to interfering in electric plants:
The JX3-BN-CAN module has to be attached to a DIN rail acc. to EN 50022-35
x 7.5.
Follow the instructions given in Application Note 016 "EMC-Compatible
Installation of the Electric Cabinet" published by Jetter AG.
The following instructions are excerpts from Application Note 016:
On principle,
physical
separation
should be maintained between signal and
power lines. We recommend spacings greater than 20 cm. Cables and lines
should cross each other at an angle of 90°.
Shielded cables
must
be used for the following lines:
Analog lines, data lines, motor cables coming from inverter drives (servo output
stage, frequency converter), lines between components and interference
suppressor filter, if the suppressor filter has not been placed at the component
directly.
Shield cables
at both ends
.
Unshielded wire ends of shielded cables should be as short as possible.
The entire shield has,
in its entire perimeter,
be drawn behind the isolation,
and then be clamped under an earthed strain relief
with the greatest possible
surface area.