6.3
Connection Monitoring at the Jetter System
Bus
Between the controller and the JX3-BN-CAN module, telegrams are regularly exchanged
via Jetter system bus. This way, the controller can monitor the connection to the
JX3-BN-CAN module. An interrupted connection can be restored by restarting the Jetter
system bus.
Monitoring Interval for I/O Modules
Register(s)
2028
Description
By means of register 2028, the time interval between two
monitoring telegrams can be set.
The monitoring interval is configured in steps of 10 ms.
0 : no monitoring
1 : Monitoring time 10 ms
2 : etc.
Access
Read / Write
Value Range
0 ... 255
Value After Reset
20 : Monitoring interval 200 ms
Comment
Connection monitoring is carried out by the following modules:
•
JX2-I/O modules
•
JX3 modules via the JX3-BN-CAN module
•
Third-party modules
•
LioN modules
•
LJX7-CSL Compactbox modules
32
Jetter AG