JX3-BN-CAN
6 Diagnostics and Administration
6.2
Diagnostics by JX3 Module Registers
Status of JX3-BN-CAN
Module Register
0
Description
The JX3-BN-CAN module reads the error bit statuses of all
connected JX3 modules in cyclic mode.
If in at least one connected JX3 module an error bit has been
set, the corresponding collective error bit is set in the status
module register.
Access Read
Value Range
16 bits, bit-coded
Value After Reset
Present state
The meaning of the individual bits in the status module register:
Bit 0:
Collective error bit 0 of the connected JX3 modules
0 =
Error bit 0 has not been set
1 =
At least one error bit 0 has been set
Bit 1:
Collective error bit 1 of the connected JX3 modules
0 =
Error bit 1 has not been set
1 =
At least one error bit 1 has been set
Bit 2:
Collective error bit 2 of the connected JX3 modules
0 =
Error bit 2 has not been set
1 =
At least one error bit 2 has been set
Bit 8:
Exceeding the time limit at cyclic data exchange
0 =
Time has not been exceeded
1 =
Time has been exceeded
0 =
This error can only be fixed by restarting the Jetter system bus.
Bit 9:
Fatal error at cyclic data exchange
0 =
No error
1 =
Fatal error
This error can only be fixed by restarting the Jetter system bus.
Bit 15:
Cyclic data exchange with the connected JX3 modules
0 =
Not active
1 =
Activated
This error can only be fixed by restarting the Jetter system bus.