5.1 Register Array for JX3 Modules
JetWeb
Example: Register and I/O Addressing of a JX3 Module in the Jetter
System Bus
Six modules, JX3-BN-CAN (33, 34), JX3-DI16 (2, 4) and JX3-DIO16 (3, 5), have been
connected to a JC-24x controller. The register and I/O numbers listed in the table below
result from the module position in the Jetter system bus.
•
In the Jetter system bus, no I/O numbers have been assigned to the JX3-BN-CAN.
•
The first JX3-BN-CAN connected to the JetControl is assigned the I/O module
number 33.
•
The first JX3 module is assigned I/O module number 2.
Register and I/O Numbers
I/O Module Number
Module
Register Number
I/O Numbers
1
JC-24X
0 ... 1999
20000 ... 49999
101 ... 116
33
JX3-BN-CAN
3310 ... 3319
-
02
JX3-DI16
3000 ... 3009
201 ... 216
03
JX3-DIO16
3010 ... 3019
301 ... 316
34
JX3-BN-CAN
3320 ... 3329
04
JX3-DI16
3020 ... 3029
401 ... 416
05
JX3-DIO16
3030 ... 3039
501 ... 516
24
Jetter AG
Содержание JX3-BN-CAN
Страница 37: ...JX3 BN CAN Appendix Appendix Jetter AG 37...