114
The Fault description without WebMotion®
Open a terminal program and give in the command
„TESM“.
F-Number
Description
Note
210
host communication, external
supervising, watchdog
Communication SMU to XENAX interrupted. Potentially, bad
shielding of encoder cable
220
data consistency/checksum
master/slave
Parameters were not uploaded correctly. Please try to
download SMU parameters again.
232
firmware version not compatible
Firmware was not uploaded correctly. Please try to
download SMU firmware again.
241
dynamic plausibility circuit encoder
Invalid state of one or more encoder signals. Check encoder
cable, possible cable break. Restart XENAX®.
243
plausibility digital signal
Invalid voltage difference of one or more encoder signals.
Check encoder cable, cable possibly broken
244
plausibility analogue signal
Unplugged encoder cable on XENAX®. Problems with the
signal connecting. Cable possibly broken.
245
encoder cable disconnected
Encoder cable disconnected to XENAX®.
246
faulty input states
There is only one active Input from the safety. There must
always be two Inputs activated for safety.
247
power active input test
Pin 9 is activated in XENAX®, this Input should not be used
with the SMU
252
motor data failure
Motor data have not been forwarded to SMU. Potentially,
there is bad shielding on the encoder cable
All other error codes are internal hardware failures. If error repeats multiple times, please contact Jenny Science.