www.janitza.de
UMG 605-PRO
72
Address
Designation
Setting range
Unit
Default
100
Collect TFTP configuration file
automatically
0 = deactivated
x = file number
0 to 9999
-
0
101
TFTP error handling
0 = in the event of an error,
the configuration menu is shown
on the display.
1 = TFTP error handling
in the device is deactivated
0 to 1
-
0
110
Measurement switch for baseline
measurement (L1 to L3)
0=4w3m, 1=4w2m, 2=4w2u,
3=4w2i, 4=3w3m, 5=3w2m,
6=3w2u, 7=3w2i, 8=2w2m,
9=2w1m, 10=4w3mhv,
11=4w2uhv,12=3w2uhv,
13=3w2mhv
0 to 13
-
0
111
Measurement switch for
supporting measurement (L4)
0=2w1n, 1=3w1m, 2=4w1m
0 to 2
-
0
112
Relevant voltage
0 = L-N, 1 = L-L
0 to 9
-
0
113
Deletes all active energy
counters and S0 counters
(1 = delete)
0 to 1
-
0
114
Deletes all reactive energy
counters
(1 = reset)
0 to 1
-
0
115
Resets all min. and max. values
(1=delete)
0 to 1
-
0
116
Flicker filters
0 - 50 Hz / 230 V,
1 - 120 V / 50 Hz
2 - 230 V 60 Hz,
3 - 120 V/ 60 Hz
0 to 3
-
0
Table Parameter list for measurement settings
Содержание UMG 605 PRO
Страница 7: ...www janitza de UMG 605 PRO 2...
Страница 19: ...www janitza de UMG 605 PRO 14...
Страница 33: ...www janitza de UMG 605 PRO 28...
Страница 37: ...www janitza de UMG 605 PRO 32...
Страница 51: ...www janitza de UMG 605 PRO 46...
Страница 53: ...www janitza de UMG 605 PRO 48...
Страница 63: ...www janitza de UMG 605 PRO 58...
Страница 75: ...www janitza de UMG 605 PRO 70...
Страница 81: ...www janitza de UMG 605 PRO 76...
Страница 85: ...www janitza de UMG 605 PRO 80...
Страница 87: ...www janitza de UMG 605 PRO 82...