UMG 605-PRO
www.janitza.de
67
Function
Symbol
Precision class
Metering range
Display range
Total active power
P
0.5
5)
(IEC61557-12)
0 to 15.3kW
0 W to 9999 GW
Total reactive power
QA
6)
, Qv
6)
0.5
5)
(IEC61557-12)
0 to 15.3 kvar
0 varh .. 9999 Gvar
Total apparent power SA, Sv
6)
0.5
5)
(IEC61557-12)
0 to 15.3 kVA
0 VA to 9999 GVA
Total active energy
Ea
0.5S
5) 7)
(IEC61557-12)
0 to 15.3 kWh
0 Wh to 9999 GWh
Total reactive energy ErA
6)
, ErV
6)
1
5)
(IEC61557-12)
0 to 15.3 kvarh
0 varh .. 9999 Gvarh
Total apparent energy EapA,EapV
6)
0.5
5)
(IEC61557-12)
0 to 15.3 kVAh
0 VAh to 9999 GVAh
Frequency
f
0.05 (IEC61557-12)
40 to 70 Hz
40 Hz to 70 Hz
Phase current
I
0.25
8)
(IEC61557-12)
0.001 to 8.5
Amps
0 A to 9999 kA
Measured neutral
conductor current
IN
0.25
8)
(IEC61557-12)
0.001 to 8.5
Amps
0 A to 9999 kA
Computed neutral
conductor current
INc
1 (IEC61557-12)
0.001 to 25.5 A
0 A to 9999 kA
Voltage
U L-N
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage
U L-L
0.2 (IEC61557-12)
18 to 1000 Vrms
0 V to 9999 kV
Power factor
PFA, PFV
0.5 (IEC61557-12)
0.00 to 1.00
0 to 1
Short-term flicker,
long-term flicker
Pst, Plt
Cl. A (IEC61000-4-15) 0.4 Pst to 10.0 Pst 0 to 10
Voltage dips
Udip
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage increases
Uswl
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Transient
overvoltages
Utr
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage interruptions Uint
Du- 1 cycle
-
-
Voltage unbalance
1)
Unba
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage unbalance
2)
Unb
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage harmonics
Uh
Cl. 1 (IEC61000-4-7) Up to 2.5 kHz
0 V to 9999 kV
THD of the voltage
3)
THDu
1.0 (IEC61557-12)
Up to 2.5 kHz
0% to 999 %
THD of the voltage
4)
THD-Ru
1.0 (IEC61557-12)
Up to 2.5 kHz
0% to 999 %
Current harmonics
Ih
Cl. 1 (IEC61000-4-7) Up to 2.5 kHz
0 A to 9999 kA
THD of the current
3)
THDi
1.0 (IEC61557-12)
Up to 2.5 kHz
0% to 999 %
THD of the current
4)
THD-Ri
1.0 (IEC61557-12)
Up to 2.5 kHz
0% to 999 %
Mains signal voltage
(interharmonics
voltage)
MSV
IEC 61000-4-7
Class 1
10% – 200%
of IEC 61000-2-4
class 3
0 V to 9999 kV
16. 11 Function parameters
16. 11. 1 Measurement in the frequency range 50/60 Hz
Measurement via current transformer ../5 A
Содержание UMG 605 PRO
Страница 7: ...www janitza de UMG 605 PRO 2...
Страница 19: ...www janitza de UMG 605 PRO 14...
Страница 33: ...www janitza de UMG 605 PRO 28...
Страница 37: ...www janitza de UMG 605 PRO 32...
Страница 51: ...www janitza de UMG 605 PRO 46...
Страница 53: ...www janitza de UMG 605 PRO 48...
Страница 63: ...www janitza de UMG 605 PRO 58...
Страница 75: ...www janitza de UMG 605 PRO 70...
Страница 81: ...www janitza de UMG 605 PRO 76...
Страница 85: ...www janitza de UMG 605 PRO 80...
Страница 87: ...www janitza de UMG 605 PRO 82...