Applying the measured current
The device:
• is intended for connecting current
transformers with secondary currents
of ../1 A and ../5 A.
• does not measure DC.
• has current measurement inputs that are
continuously loaded with 6 A or loaded
with 100 A for 1 second.
Proceed as follows to connect measured
current to the device:
1. Connect the currents to be measured
to voltage measurement inputs I1 to I4.
2. Short circuit all current transformer outputs
except for one.
3. Compare the currents displayed by
the device with the applied current.
• Bearing in mind the current transformer
conversion ratio, the current displayed
by the device must correspond
to the current input.
• The device must display approx. zero
amperes in the short circuited current
measurement inputs.
The current transformer ratio is factory-set
to 5/5A and must be adapted to the current
transformer used if necessary.
9. 6
Checking the power measurement
Short-circuit all current transformer outputs
except for one and check the displayed
power outputs.
The device may only display one power
output in the phase with a non-short-
circuited current transformer input. If this
is not the case, check the connection of
the measured voltage and the measuring-
circuit current.
If the power figure is correct but the power
sign is negative, connections S1(k) and S2(l)
on the current transformer may be mixed up
or they are supplying active energy back to
the network.
Содержание UMG 605 PRO
Страница 7: ...www janitza de UMG 605 PRO 2...
Страница 19: ...www janitza de UMG 605 PRO 14...
Страница 33: ...www janitza de UMG 605 PRO 28...
Страница 37: ...www janitza de UMG 605 PRO 32...
Страница 51: ...www janitza de UMG 605 PRO 46...
Страница 53: ...www janitza de UMG 605 PRO 48...
Страница 63: ...www janitza de UMG 605 PRO 58...
Страница 75: ...www janitza de UMG 605 PRO 70...
Страница 81: ...www janitza de UMG 605 PRO 76...
Страница 85: ...www janitza de UMG 605 PRO 80...
Страница 87: ...www janitza de UMG 605 PRO 82...