EVO controller
Manual
www.jakkagroup.com
4
AIR POST-TREATMENT CONTROL
The control can run an air post-treatment system with either a water coil or an electric resistance. A box representing the post treatment
appears on the supply airflow. The symbol inside, if red, indicates that heating is being worked on. While if blue indicates that it is
working in cooling. If there are two post-treatment elements, the boxes become two with the corresponding red \ blue symbols for
each one. The writing on-off (which only appears in the presence of a post-treatment) indicates only that the function is enabled \
disabled. So even if we find it “on “the post treatment it is not necessarily active.
SET POINT TEMPERATURE
The temperature set-point is given by the thermometer icon (located at the bottom right of the screen like images next paragraph)
that can be red (heat mode) or blue (cooling mode). When the bottom icon is selected, the desired interior temperature set-point (Ts)
function is accessed: the user can increase the Ts value by the up arrow key or, vice versa, reduce it by the down arrow key. With the
central button, which appears at first, is possible to deactivate the set-point (and so treatment air). Once the desired value is achieved,
the selection is confirmed by pressing OK. Ts can take values between 5.0°C and 30.0 °C with 0.1°C steps. The icon also appears when
a post-treatment system is not installed, in this case the set is used to manage the by-pass in free-heating \ cooling. The temperature
reference is return (Tr).
Post-heating on
Post-heating off
Post-cooling on
Post-cooling off
Post-heasting modification