Manual
EVO controller
27
www.jakkagroup.com
8502
(100 bit/s)
R/W
DEFAULT = 96
R/W
Installation must be carried out by expert staff. For the best operation, the remote panel must be fixed to an indoor wall about 1.5 m
above the floor, far from heating sources (radiators, stoves, etc.), and must be not exposed to direct sun rays. It must be not installed
near doors, which might damage the electronics if slammed. The maximum distance from the main electric box is 70m.
Access limited by password installer, to modify write before it in register 855
*
** For writing, set before Bit 14 \ 15 of Reg 5 = 1, alternatively web server or touch panel
INSTALLATION
CONTROL PANEL WIRING
Connection Tcp-ip \Rs485 additional card
Remote panel: rear view
SERVICE-DATA
Connect the power supply to the 24V and G terminals, matching the correct polarity. Connect the BUS to the S terminal. Using a min.
0.3 mm2 section shielded cable is recommended. In case of communication errors, check the connections between the remote
panel and the electronic card. For panel with Modbus tcp-ip connect the Ethernet cable in the connector, with rs485 additional card
use 3x0,3mm2 shielded cable.
BAUD RATE*
TIME OUT*
PASSWORD
(SEC)
DISCONNECTION TIME
DEFAULT = 10 SEC.
65535 DISABLES DISCONNECTION IN CASE OF FAILURE
TO READ REGISTERS
8503
DAY * **
1 (MONDAY) -7 (SUNDAY)
SET DAY
8555
HOUR * **
1-24
SET HOUR
8556
MINUTES * **
0-59
SET MINUTES
8557
8559
R/W
INSTALLER:5678
INSERT TO MODIFY PARAMETERS MENU INSTALLER