EVO controller
Manual
www.jakkagroup.com
24
1
SW_PN_0
SW TYPE 0
R
14
SPEED_
BALANCE
67-150 (%)
R/W FAN UNBALANCE (EXHAUST = % DELIVERY)
2
SW_PN_1
SW TYPE 1
R
3
SW_PN_2
SW VER 0 (AAMM)
R
4
SW_PN_3
SW VER 1 (DDPP)
R
PCB RESET NOTICE BIT:
PCB RESET NOTICE BIT:
DEFAULT=1 , IF SET AT 0 AND A 1 IS FOUND LATER ON,
IT MEANS A RESET OF THE CARD HAS TAKEN PLACE.
5
20
24
0-199 (500h)
R/W
25
0-199 (500h)
R/W
26
0-199 (500h)
R/W
27
0-199 (500h)
R/W
CO MMANDS
51
R/W
FOR VARIABLE SPEED VERSION:
0-100 % ; 101=TIMER ; 102=AUTO.
FOR THREE SPEED VERSION:
1-2-3 ; 4=TIMER ; 5=AUTO .
FOR CAV\COP UNITS:
PASCAL-M3\H
TIMER(65634)
AUTO(65535).
FAN SPEED SET-POINT:
FOR VAV UNIT:
0-100 % ; 101=HOUR PROGRAM; 102=AUTO.
FOR UNIT 3 SPEEDS:
1-2-3;
4= HOUR PROGRAM;
5=AUTO.
FOR CAV \ COP UNITS:
PASCAL-M3\H
TIMER=65634;
AUTO=65535.
ADDRESS
WORD ID
FORMAT
CONFIGURATION
R/W
VALUE DESCRIPTION WHEN SWITCHING THE UNIT ON OR OFF
REMOTE
CONTROL
PARAMETER
FLAGS**
UNIT_1_M
AX_FILT
HOURS**
HOUR FILTERS
ALARM THRESHOLD UNIT1
HOUR FILTERS
ALARM THRESHOLD UNIT2
HOUR FILTERS
ALARM THRESHOLD UNIT3
HOUR FILTERS
ALARM THRESHOLD UNIT4
UNIT_2_M
AX_FILT
HOURS**
UNIT_3_M
AX_FILT
HOURS**
UNIT_4_M
AX_FILT
HOURS**
SPEED_SE
T_POINT**
B00: R/W DEVICE_RESET (1=RESET)
B01: R TERMINAL_ACTIVE (1=ACTIVE)
B04: R/W CONNECTION_LOST (1=LOST)
B13: R/W CMD DEVICE RESET (1=RESET)
B14: R/W WR_APP_CONF (1=WRITE PENDING)
B15: R/W WR_SP (1=WRITE OENDING)
DISCONNECTION HAS TAKEN PLACE.
DEFAULT=0; IF SET AT 1, THE CARD IS RESET.
ENABLE BIT FOR STORING CONFIGURATION IN
NOVRAM (IF=1 AFTER WRITE REG)
ENABLE BIT FOR STORING SET-POINT IN
NOVRAM (IF=1 AFTER WRITE REG)
SETTING SEA SON BYPASS B00-01
0=UNDEF./AUTO
1= WINTER 2=SUMMER
UNIVERSAL (B02 B03)
1= MANUAL OFF
1=MANUAL=ON
BIT ON-OFF
DEHUMIDIFIER
BIT ON-OFF
FANS
BIT ON-OFF
AIR POST TREATMENT
R/W
B00-01: R/W SEASON
0: SEASON_ND
1: SEASON_WINTER
2: SEASON SUMMER
B02-03: R/W BYPASS
0: BYPASS_AUTO
1: BYPASS_OFF
2:BYPASS_ON
B04: DEHUMIDIFIER SWITCH OFF
0: DEHUMIDIFIER ON
1: DEHUMIDIFIER OFF
B05: SPEED SWITCH OFF
0: SPEED ON
1: SPEED OFF
B06: POST TEMPERATURE
MANAGING SWITCH OFF
0: POST ON
1: POST OFF
B02: R TERM_RS485_ACTIVE (1=ACTIVE)
CONNECTION TO TERMINAL
CONNECTION TO TERMINAL RS485
DISCONNECTION NOTICE BIT:
DEFAULT=0, IF AT 1 IS FOUND LATER ON, IT
MEANS
SW MODEL
SW MODEL
SW VERSION
SW VERSION