Manual
EVO controller
17
www.jakkagroup.com
AutoMin% corresponds to the input signal percentage value for which fans must run at the minimum speed,
AutoMax% corresponds to the input signal percentage value for which fans must run at the maximum speed.
PARAMETERS AVAILABLE IN THE INSTALLER MENU
Language
With this parameter, you can select the language of all menus (except for the Factory menu, which will always be in English).
GB English language (default)
FR French language
ES Spanish language
IT Italian language
NL Dutch language
DE German language
HU Hungary language
DK Danish language
PT Portuguese language
SI Slovenian language
Auto1\2
With this parameter, you can configure a device that automatically adjusts the fan speed. See the wiring diagram for the connection
of the device
External signal. The fan speed will be controlled through an external 0-10V analog signal (default value); if the external signal takes the
0V value, the control will indicate a problem with the source of the external signal. For a unit equipped with adjustable speed fans.
FAN speed
AutoMin%
INPUT signal
AutoMax%
MAX
MIN
For a unit equipped with 3-speed fans.
SP.1,2% SP.2,3% and
Δ
values depend on the values of parameters AutoMin% and
AutoMax% according to the following formulas:
FAN speed
SP.3
SP.2
SP.1
SP.1,2%
INPUT signal
-∆
|
+∆
SP.2,3%
-∆
|
+∆
Automax% - AutoMin%
SP. 1,2% = + AutoMin%
10
Automax% - AutoMin%
12
5
,3
x (AutoMax% - AutoMin%) + AutoMin%
SP. 2,3% =
SP.
+
7
2
∆
=