Manual
EVO controller
13
www.jakkagroup.com
ALARMS MENU: DISPLAY OF THE ALARM STATUS
Signaling an alarm: external air temperature probe
Alarms menu
If an alarm is being signaled, you can reach the specific menu directly by touching the screen. Otherwise you must select the Alarms
item in the menu selection page and press OK. If the control is interlocked to several units (master/slave mode), you must select the
unit you want to monitor (see Status menu), otherwise you direct access to the detail alarms page.
If the control detects an abnormal status, the latter is indicated in the main control screen by a specific flashing icon and a red writing
at the top of the screen (Call service o DirtyFilters). If the alarm is detected when the screen is in stand-by mode, the display flashes at
about 10-second intervals. Alarms on pressure sensors are available for machines with cop/cav kits only.
LIST OF ALARMS
Parameter
Status
Val
Communication
ok
Te (external)
ko
The external air temperature sensor works properly
Problem with the external air temperature sensor:
1) check electrical connections of the temperature probe (see wiring diagram);
2) if the problem is not solved, replace the temperature probe
3) if the problem is not solved, replace the electronic card.
ok
Configuration
ko
ok
The configuration of the digital input is ok
ko
The communication between the machine cardsand the remote control panel
works properly
Problem with the communication among cards and remote panel:
1) check electrical connections between electric panel and remote panel
(see wiring diagram);
2) if the problem is not solved, check electrical connections between the
cards (see wiring diagram);
3) if the problem is not solved, check the dipswitch position in both cards
only 1 unit: X540 only 1=on ; X531 only 2= on, X541 card all off .
4) if the problem is not solved, replace the electronic cards.
The configuration of the digital input is wrong, this happen when a new
control panel is mounted on an old card with digital input configured. To
solve the problem reconfigure in menu factory EXTDI.