JBE-P2L1 Panel Manual V1.2 EN
Page 37
Release Date: January 5, 2021
Rev 01
Figure 17: Example Input Action
Programming
the “Outputs” triggered by an action
Up to 16 output groups can be activated by a single action. This includes siren output groups (SND-001) and
(FR-002).
For each activation, enter the following parameters:
Activation group
: Select the group to activate when the input rule is fulfilled. Choose between group 001
to 400.
Delay
: Select the seconds of delay between the moment in which the input condition was fulfilled and the
activation of the input. Note that these delays are fix and are not activated/deactivated by the delays on/off
button. Select from 000 to 600 seconds of delay. Selecting 000 means immediate activation.
Hold
: Populate this field if you want outputs to be active for just a brief period of time (up to 63 seconds).
Select for how many seconds do you want the output to activate. Leaving the default value 000 means that
outputs will activate for an indefinite duration (i.e. until the panel is reset).
Warning: EN54 does not allow automatic muting of siren groups or FR outputs. Activation groups 001 and
002 must remain active until the manual intervention of the user.