JBE-P2L1 Panel Manual V1.2 EN
Page 26
Release Date: January 5, 2021
Rev 01
5.5.1 Reset
To reset the Draco panel and clear all the current system settings/events, press Reset button to go back
to original standby condition. The user interface will prompt for the operator password before performing this
action.
5.5.2 Activate Delays
User can press the Delays ON/OFF button to activate/deactivate the sounder and fire brigade output
delays. The user interface will prompt for the operator password before performing this action.
Note that the day/night schedule can also activate and deactivate the delays at a fixed schedule. Manual
and scheduled delay activation modes are compatible with each other.
5.5.3 Operate menu
Under the Operate menu, personnel with user access level 2 can perform tasks related to testing and
disablements, such as run tests on zones, output groups, keyboard and indicators, and disable zone, device
or output groups accordingly. This menu also gives access to adjusting the date and time for the panel.
Users can also review the serial numbers and firmware versions of the control panel from this menu.
The sub-menu choices from the Operate menu is as follows:
1.
Test zone
2.
Test output group
3.
Keyboard test
4.
Indicators test
5.
Disable zone
6.
Disable output group
7.
Disable device
8.
Set time and date
5.5.3.1 Test zone
This menu allows setting zones in and out of the test functional condition.
After entering user access level 2 password, use the directional keypads to move to the desired zones and
select 1 for yes and then press the Confirm key to test the designated zone(s).
When an alarm is received from a zone under te
st, it will be presented for 10 seconds in the panel’s user
interface and it will disappear. Alarms from zones under test will not activate outputs. These alarms will be
logged in the event log.
5.5.3.2 Test output group
This menu allows testing the activation of an output group. A test will activate temporarily all the output
devices associated to a group.
After entering user access level 2 password, enter test output group from operate menu. The operator can
select a specific output group (sounder group, fire routing group) from the main sub-menu by entering in a 1
for yes using the directional keys and the numeric keypad. A programmable group or field devices can be
selected by pressing F2 or F3.