JBE-P2L1 Panel Manual V1.2 EN
Page 14
Release Date: January 5, 2021
Rev 01
Figure 9: Battery Connection Location for 17 Ah
4.3
Commissioning using the Wizard
The Draco fire panel features a commissioning wizard. This wizard will guide the installer step-by-step to
achieve a functional basic configuration. More sophisticated configurations can be achieved by exercising
the configuration options described in section 5.6. The commissioning operations are restricted to user
access level 3 and shall be conducted by trained operators only.
Before starting a commissioning, verify that the steps described in section
Error! Reference source not
found.
have been completed. That is, that the fire panel is safely wall-mounted, connected to all field wiring
and energized.
4.3.1 Initiating the wizard
In order to initiate the commissioning process:
1.
Push the home button
2.
Push F5 “Install”. The system will prompt for the level 3 password (the default password to
access this level is
1111111111
).
3.
Select the first option in the menu (1.Wizard).
4.
Select the first option in the menu (1.Install).
The wizard will guide the user through the following steps:
4.3.2 Auto-registration of loop devices
This routine will scan the detection loops and will identify all addresses connected, in a process that can take
2 minutes.
Verify that all the devices planned in the installation have been detected.
Note: All field devices must have been previously programmed with the JBE-AT1 Address
Programmer. Once programmed, you can start the registration / reading process described above
from the control panel.
4.3.3 Assign devices to zones
After auto-registration, all devices will have been assigned to zone 1. Use this menu to select the desired
detection zone for each initiating device (see 4.5.1.3).