JBE-P2L1 Panel Manual V1.2 EN
Page 30
Release Date: January 5, 2021
Rev 01
5.6
Operations available only to users with access level 3
This section describes in detail what functionalities of the panel that a user access level 3, either installer or
maintenance/commissioning personal, can have. For this user access level, the menus for Adjust and Install
are available.
5.6.1 Adjust Menu
The Adjust Menu tree contains operations typically restricted to personnel trained in the installation &
maintenance of fire systems. These operations will typically be used only during commissioning, expansion
or maintenance of the fire installation.
To enter the adjust menu, the 10-digit password for user access level 3 is required. By pressing the Home
key and then the F4, user can navigate the “Adjust” menu tree by using both alphanumeric keypad and
function keys.
The sub-menu choices from the Adjust menu is as follows:
1.
Manual device registration and de-registration
2.
Set address description
3.
Assign devices to zones
4.
Delays and linkage to SND/FR by zone
5.
Set loop class (A or B)
6.
Assign device to activation group
7.
Enter maintenance company details
8.
View analog value curve of detector
9.
Configure Day/night mode
0.
Setup printer
5.6.1.1 Registro o borrado manual de dispositivos de lazo
User can manually enter the loop number, address and device type (shown below) to register or delete the
device. Device types are classified into 8 categories so that users can select the type to delete and / or
register.
01. Smoke Det.
03. MCP
05. I/O Module
07. Sounder
02. Heat Det.
04. Input Module
06. Combo Det.
08. Output Module
5.6.1.2 Set address description
The user can manually add a description for each device through this submenu. Both the numeric and
alphabetic keyboard are available in the interface for the user to enter the data. Remember to save the
inserted description before switching to the next device.
By pressing F2 or F3, the user can switch to the next or previous device.
5.6.1.3 Assign devices to zones
By entering this sub-menu, users can assign specific devices to designated loop. The column Current
indicates the current zone the device has been assigned to. A new zone number can be assigned to each
device by changing the number under the Set column and pressing F5 to confirm the changes.