background image

Installation manual: Oasis security system JA-80K  

- 3 - 

 MKE51801

 

 

System installation shall only be undertaken by qualified 
technicians holding a training certificate issued by an authorized 
distributor. The manufacturer cannot be held responsible for any 
damage or consequences related to the improper or incorrect 
use of this product. 

 

1.  Control panel architecture 

 

  The control panel has 

50 addresses

 (01 to 50), meaning that 

up to 50 wireless devices can be enrolled i.e. detectors, 
keypads, keyfobs, sirens etc.  

 When triggered, a detector sends a so-called natural signal 

which dictates what the reaction of the control panel should 
be.  E.g. the natural signal of a door contact or PIR detector 
can be an instant or delayed alarm which is selectable by a 
DIP switch inside the detector. A keyfob, for instance, sends 
signals for set (arm), unset (disarm) and panic.   

o

 The control panel is factory-set to perform natural reactions 

according to the signals sent from wireless devices. By 
programming the addresses of the devices in the control 
panel, it is possible to define how the control panel reacts to 
individual wireless devices. E.g. a door detector assigned to 
address 15 could trigger a panic reaction, and a keyfob 
button using address 24 could cause a fire reaction etc. 

 Wireless devices can be assigned to 3 sections: 

A

,

B

 or 

C

Assignments to sections either have an effect when partial 
setting is used e.g. only A is set, AB is set, or ABC is set 
(which, for example, would be suitable for homes where A 
could mean afternoon setting, AB night setting and ABC total 
setting), or if the system was split into two independent 
partitions A and B, with a common section C. In the second 
case, each A or B section can be set individually, and C is 
automatically set when both A and B have been set by users. 
This would be suitable for two independent families in a single 
house, or two companies in one building.   

  There are two hard-wired inputs with programmable functions 

assigned to addresses 01 and 02. If these two inputs are not 
used, the two addresses can be used to enroll wireless 

devices.

 

 Hard-wired inputs are also provided by some 

wireless devices, such as keypads, door detectors, and PIR 
movement detectors.  

 The control panel has two alarm outputs: 

IW

 = internal 

(indoor) warning and

 EW

 = external (outdoor) warning. Both 

these signals are also available as wireless signals. 

 There are two programmable outputs in the control panel,

 

PGX and PGY 

whose functions can be configured

.

 The PG 

outputs are not only available as physical control-panel 
terminals, but also as radio signals for the control of UC and 
AC receiver outputs. 

  The system can be operated by user codes or user cards. The 

system can recognise up to 50 different users. The system 
can also be operated by wireless keyfobs, and if the control 
panel is equipped with a suitable communicator it can also be 
remotely controlled by mobile phone or the Internet. 

  It is possible to program different reactions to access codes or 

access cards and if the system is split, it is possible to 
program which part of the building is accessible by a particular 
code or card. Each of the possible 50 users can have his own 
4-digit access code and/or access card. Setting (arming) and 
unsetting (disarming) is possible by card or code, and if a 
higher security level is needed it is possible to make it 
compulsory to confirm the validity of a card by code entry. 

 

Programming the system 

is possible

 

by Oasis keypads such 

as  the wireless JA-80F or the hard-wired JA-80E, and also by 
computers running ComLink software. Further options offer 
programming by mobile phone or the Internet. 

  There is a power supply in the control

 

panel

 

and space for a 

12V,  1.3 to 2.6 Ah

 back-up battery.

 

 

 To connect a hard-wired keypad or a computer, the control 

panel is equipped with a digital bus provided by terminals and 
RJ connectors.  

 The control panel can be equipped with an optional 

communicator to provide external communications to the 
system. The JA-80Y GSM/GPRS communicator or JA80-
V LAN and phone line communicator both allow data to be 

Communicator

Main board 

Transformer

Back-up battery

Mains terminal

Digital bus connector

GSM antenna

tamper switch

SIM card

LEDs

Antenna

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: