background image

Installation manual: Oasis security system JA-80K  

- 13 - 

 MKE51801

 

 

12.17.  Exit delay beeps while partially setting 

(arming) 

 

The exit delay caused by partial setting, e.g. using the A or B 
key, can also be indicated by keypad beeps and internal-siren 
beeps. The beeps get faster in the last 5 seconds. 

 

3 4 1

 Beeps 

enabled

 

3 4 0

 Beeps 

disabled

 

 

Factory default setting:

 

Beeps disabled

 

12.18.  Entrance delay beeps 

 

The entrance delay can be indicated by keypad beeps and 
internal-siren beeps: 

 

3 5 1 

Beeps 

enabled 

3 5 0

 Beeps 

disabled

  

 

Factory default setting:

 

Beeps enabled

 

 

12.19.  Setting (arming) confirmation by wired-siren 

chirp 

A hard-wired siren connected to the IW terminal of the control 
panel can audibly indicate setting by one beep, unsetting by two 
beeps and unsetting after an alarm by three beeps. Four beeps 
mean an invalid attempt at setting the system has occurred.  

 

3 6 1

 Chirps 

enabled

 

3 6 0

 Chirps 

disabled

  

 

Note:

 In JA-80L wireless sirens, this function can be individually enabled 

for each siren. (see the siren manual). 

 

Factory default setting:

 

Hard-wired siren chirps

 disabled

 

 

12.20.  Sirens always sound during audible alarms 

Using this sequence it is possible to disable internal and external 
sirens (IW and EW) if any part of the system is unset (partial 
setting), i.e. when someone is home. 

 

3 7 1

  Sirens always sound during audible alarms 

3 7 0

  Sirens only sound during audible alarms when all 

sections are set, i.e. no one is home 

 

Factory default setting: 

Sirens always sound during audible 

alarms

 

12.21.  Wireless siren alarm enabled (IW and EW) 

This setting is for enabling and disabling wireless sirens in the 
system:   

 

3 8 1

  wireless sirens enabled 

3 8 0

  wireless sirens disabled 

 

Note:

 This setting has no effect on wired output terminals. 

 

Factory default setting:

 wireless sirens enabled 

 

12.22.  Auto-bypass user approval via the 

 key 

 

The system has a built-in auto-bypass function so that if any 
number of detectors are being triggered during setting (arming) 
then they will be bypassed and ignored automatically. 
If auto-bypass approval by the user is disabled, then during 
setting (arming) the system notes which detectors are currently 
triggered and automatically bypasses them without consulting 
the user.  
If however, auto-bypass user approval is enabled, then during 
setting (arming), the system notes which detectors are currently 
triggered and displays informative text on the keypad and only 
bypasses them if the user approves the bypassing by keying in a 

 within 6 seconds of being notified. 

 

3 9 1 

Approval is requested from the user 

3 9 0

  Bypassing occurs automatically without user approval 

 

Notes regarding setting the system with (a) triggered detector(s): 

 

Details on currently triggered detectors can be viewed by pressing the 

?

 key (e.g. open doors or windows). 

 

If a wireless keyfob is used to set the system and auto-bypass user 
approval is enabled, the system will set without bypass approval, i.e. 
setting by keyfob does not trigger an approval request.  

 

The automatic bypass of a detector will end  after the detector has 
been de-triggered (for example if a door is closed) 

 

If auto-bypass user approval is enabled and Service mode is being 
exited while a detector is being triggered, the installer will be notified 
about the bypass. The installer can then approve the bypass by 
pressing #  twice. 

 

To comply with the EN-50131-1standard 391 should be set. 

 

Factory default setting:

 

Bypassing occurs automatically 

without user approval

 

 

12.23. Final-door 

detectors   

In this mode, up to 5 detectors can be defined as final-door 
detectors and assigned to addresses 01 to 05 or 46 to 50 in 
order to make leaving a building much easier, especially via a 
garage:  

 

65x 

 where x:  

0 = none,  
1 = detectors on addresses 01 to 05, 
2 = detectors on addresses 46 to 50 

 

 

 

Description of final-door detector mode: 

  If a final-door detector is used in the system then the value of 

x for exit delay programming is multiplied by 30 s (see 12.1) 
thereby extending the delay, and if an entrance delay is 
triggered by a final-door detector then the value of x for the 
entrance delay is also multiplied by a larger value of 30 s. 

  A final-door detector should be programmed to have a natural 

reaction.  

 Door/window detectors, hard-wired control panel inputs or 

hard-wired inputs in the wireless keypad unit can be used as 
final-door detectors. 

  If a final-door detector is used for a garage door, no instant 

detectors should be inside the garage. Next-delay detectors 
would however be acceptable. 

 

Setting (arming) the system with a final-door detector 

 After entering a request to set the system, an exit delay of 

between 30 to 270 seconds will begin and be indicated.  

 If a final-door detector is triggered during the exit delay, the 

exit delay will be extended by the time in which the detector is 
still triggered. So, if for example, the door is left continuously 
open, the exit delay will never end. 

  If a final-door detector is de-triggered, the system will wait five 

more seconds during which beeping gets faster, and if the 
door is not opened again during this short period, the exit 
delay will terminate and the system will be set immediately. 

  The duration of the exit delay therefore depends on the time 

the final door stays open. For instance, in winter if the 
driveway in front of a garage needs to be cleared of snow 
there will be plenty of time to do it, and in summer when 
garages can be exited easily and therefore quickly, the exit 
delay can be rather shorter. The exit delay only depends on 
the length of time  the garage door is left open. 

 If no final-door detectors are triggered during the exit delay, 

the system will provide an exit delay and then set.  

 If the final door detector stays continuously triggered, an 

endless exit delay will result with the system never being set. 
This means all delayed and next-delayed detectors will not be 
set (armed). 

  If there are multiple final-door detectors in the system, the exit 

delay is extended if any of them is triggered and ends after all 
final-door detectors have been de-triggered. 

 

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: