background image

Installation manual: Oasis security system JA-80K  

- 15 - 

 MKE51801

 

 

 

Factory default setting:

 only 3 minutes of display time 

 

12.29.  Tamper alarm if unset 

According to EU legislation an unset (disarmed) system should 
not audibly sound a tamper alarm if tampering occurs. If the 
audible indication of tamper alarms is required while the system 
is unset (disarmed) then this can be enabled by the following 
sequence:  

6841

  audible tamper alarm even for an unset system 

6840

  silent tamper alarm for an unset system  

 

Notes:  

 

Even if tamper alarms are silent, they are still recorded in the control 
panel memory and reported to the end user by SMS, and also to the 
ARC if used. 

 

If the sequence 370 has been programmed, then tamper alarms will 
be silent if the system is unset or partially set. 

 

Factory default setting:

 silent tamper alarms for an unset 

system 
 

12.30. Engineer 

reset 

This is a special function requested by the DD243 standard. It can 
only be used when the alarm system is connected to an alarm-
receiving center. When a confirmed alarm is activated the control 
panel is completely blocked – it cannot be operated by any user, 
master or service code until an engineering reset is performed by 
an ARC code. 

 

 

6861 

Engineer reset enabled

 

6860 

Engineer reset disabled

 

 

Factory default setting

Engineer reset

 

disabled

 

 

Notes:  

 

To enable the confirmation of intruder alarms (requires two detectors to be 
triggered in different zones within a definite period) – use sequence 3 2 1  

 

Reporting to ARCs must be locked by a digital code. 

 

The keypad shows the text “Eng. reset req’d” and the system stays 
blocked until the ARC code is used via the communicator (see manual). 

 

The feature is supported when a JA-80Y version XA61008 or higher, or a 
JA-80V version XA64005 or higher is installed. 

 

12.31.  Recording PG output activation to memory 

The activation of PGX and PGY outputs can be recorded in the 
control panel’s memory (for example if the outputs are used for 
access control). This can be enabled by the following sequence:    

 

6851

 enabled 

6850

 disabled 

 

 

 

Factory default setting:

 recording enabled 

 

12.32.  Annual check notification 

This sequence enables the user and installer to be notified of the 
necessary time for an annual technical check: 

 

6900

 notification 

disabled

 

6901

 notification 

enabled

 

 

Notes:  

 

An annual technical inspection notification is displayed as text on the 
keypad display and can also be sent as an SMS to the end user 
and/or installer and/or as a report code to an ARC, if used. 

 

Annual technical inspection notification text disappears on entering 
Service Mode 

 

When this notification is enabled, exiting Service Mode will cause a 
notification to occur in the next year on the first day of the month in which it 
was set. (e.g. if you set the annual check notification on the 15th October 
2007, the notification is displayed on the 1st October 2008.) 

 

When this notification is enabled, exiting Service Mode will cause a 
notification to occur every twelve months later (the same day and 
month). 

 

If you wish to receive a notification earlier than a year later, change 
the  internal clock settings to the day and month you prefer before 
exiting Service Mode by entering 4hhmmDDMMYY, and then re-
adjust the clock to the correct time in maintenance mode. By tricking 
the system this way, you can be notified on the desired date. (see 
12.45, entering and exiting maintenance mode does not change the 
notification date). 

 

Example

: If the date is 10 January 2007 and you wish to receive a 

notification 6 months later on 10 July 2007, while still in Service Mode  
change the system clock to 10 July 2007, i.e. the day and month of the 
desired notification date. Then exit Service Mode and re-adjust the clock 
to the correct time in maintenance mode. 

 

Factory default setting:

 Annual inspection notification disabled. 

 

 

12.33.  Only single alarm indication    

If this function is enabled, then only one intruder alarm may be 
indicated at a time. Once an intruder alarm has been triggered 
and has still not ended, then no more alarms can be indicated 
no matter how many more times triggering occurs. After the 
alarm has ended, the system is then ready  to indicate the next 
single intruder alarm. 

This is to limit the number of SMS reports sent if hard-wired 

PIR detectors capable of being frequently triggered are installed 
in the system and the system is not unset (disarmed) properly 
when someone enters the building. 

 

6 9 1 0

  multiple simultaneous intruder alarms allowed   

6 9 1 1

  single intruder alarm allowed only 

 

 

Note: 

Apart from this limitation in the number of simultaneous 

intruder alarms, the system also checks to see if any detector is 
triggering multiple alarms during the period in which the alarm is 
set. Any such undesirable detector is then 

automatically 

bypassed

 every time the system is set, if it has caused at least  

four alarms in a row

 

Factory default setting:

 

multiple simultaneous intruder alarms 

allowed 

 

Note: A panic alarm can always be triggered with no limits 
(except when in service and maintenance modes).

 

 

12.34.  Setting (arming) by service code 

    

Using this sequence, the installer can be authorized to set and 

unset the system by means of a valid service code. This feature 
should only be enabled with the explicit approval of the master 
code holder (system administrator):   

 

6 9 2 0

   disabled 

6 9 2 1

   enabled

 

 

Factory default setting:

 

disabled

 

 

12.35.  Audible panic alarm   

If enabled, panic alarms can be indicated by internal and 
external warning devices (sirens on IW and EW):     

6 9 3 0

  

silent 

panic alarm  

6 9 3 1  audible 

panic alarm

 

 

Note:

 If the sequence 370 is used, panic alarms are silent if any section 

of the system is unset. 

 
Factory default setting:

 

silent

 

panic alarm

 

 

12.36.  Higher control-panel receiver-sensitivity 

If enabled, this feature can extend the communication range 
between the control panel and its wireless devices if there is no 
radio frequency interference in the premises.     

6 9 4 0

  

standard 

control  panel sensitivity  

6 9 4 1  higher 

control  panel sensitivity

 

 

Note: 

The sensitivity of the control panel receiver should only be 

increased if there is no RF interference as the radio range would only be 
reduced if interference was present.

  

 

Factory default setting:

 

standard 

control  panel sensitivity

 

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: