Installation manual: Oasis security system JA-80K
- 11 -
MKE51801
12.4.
Alarm duration time
This parameter limits the duration of a triggered alarm. After the
alarm state expires, the control panel will return to its previous
state, i.e. as before the alarm occurred. The alarm state can also
be terminated by an authorised user. To program the alarm
duration enter:
22x
where
x
is
a number from 0 to 9 determining
the alarm duration: 0 = 10 s, 1 = 1 min., 2 = 2
min. up to 8 = 8 min., 9 = 15 min.
Note: There can be up to 5 different alarms in the system: intruder,
tamper, fire, panic, and technical alarm
.
Example:
Alarm duration of 5 min. = sequence 225
Factory default setting:
4 minutes
12.5.
PGX and PGY functions
The functions of PGX and PGY can be programmed by entering
sequences:
2 3 x
for PGX
2 4 x
for PGY
where
x
determines the PG function or the event which triggers
a change of PG state:
x
Unsplit system
Split system
0
Completely (ABC) set
= PG on
Alarm A = PG on
1
Anything set = PG on
Alarm B = PG on
2 AB
set
(not ABC)
= PG
on
Entrance delay A = PG on
3
Fire alarm = PG on
Entrance delay B = PG on
4
Panic = PG on
A set = PGX on, B set = PGY on
5
Any alarm = PG on
Panic A = PGX on
Panic B = PGY on
6
AC dropout = PG on
Fire = PGX on, dropout =PGY on
7* ON/OFF
8* 2 seconds pulse
* The ON/OFF and 2 second pulse functions can be controlled from
the keypad by keying in * 8, *9 or using the arrow keys
(see
12.27) or they can be operated by a code or card. These PG output
functions can also controlled by signals from keyfobs or detectors (see
12.41).
Notes:
•
The PGX and PGY outputs are not only provided as control panel
terminals, but the signals are also wirelessly transmitted for UC and
AC modules.
•
The status of PGX and PGY outputs can be displayed by pressing
the “
?”
key. The names of the outputs can be edited – see 12.47.
Example (for unsplit systems):
Assigning an ON/OFF function
to the PGX output = sequence 237. Assigning a panic function to
the PGY output = sequence 244.
Factory default setting:
PgX= ON/OFF, PgY= anything set
12.6.
Changing telephone numbers in maintenance
mode
If the control panel is equipped with a JA-80Y, JA-80V or JA-80X
communicator, then this sequence enables the
holder of the
master code (system administrator)
to program telephone
numbers for alarm reporting in maintenance mode.
Programming telephone numbers is the same as in Service
mode (see communicator manual):
2 5 1
programming
enabled
2 5 0
programming
disabled
Factory default setting:
programming disabled
.
12.7.
Radio interference indication
The control panel is capable of detecting and indicating radio
communication jamming. If this function is enabled, any radio
jamming longer than 30 s will trigger fault indication.
2 6 1
enabled
2 6 0
disabled
Factory default setting:
disabled
.
Note:
In some places the system can be permanently or occasionally
affected by radio interference, e.g. by nearby radar stations, TV
transmitters etc. In most cases the system can tolerate such effects, but
with this anti-jamming function disabled.
12.8.
Radio communications supervision
If enabled, the control panel can routinely check wireless
connections to its devices. If communication with a particular
device is lost, the control panel can communicate a fault indication
to the user:
2 7 1
indication
enabled
2 7 0
indication disabled
Notes:
•
In the Oasis system, communication is checked every 9 mins.
•
In detectors used for car protection, (JA-85P, JA-85B) it is possible to
disable radio communication supervision. It allows car detectors to be
excluded from supervision to avoid alarm triggering when driving the
car away from the system.
•
Random dropouts in communication can occur in some installations
near e.g. airports or TV towers. The system is still reliable in such
situations as high-priority transmissions are repeated often. We
recommend disabling communications supervision in cases like this.
Factory default setting:
supervision disabled.
12.9. RESET
enabled
If resetting is enabled, it is possible to return the control panel to
its original factory-default settings via the reset link on the main
board. (see section
9.
).
2 8 1
RESET
enabled
2 8 0
RESET
disabled
Warning:
If resetting is disabled and the service code has been
forgotten, it would no longer be possible to enter Service mode. If this
happens, send the control panel back to the manufacturer.
Factory default setting:
RESET enabled.
12.10. Enrollment to a sub control panel for setting
(arming) control
If the control panel has another Oasis control panel enrolled
as a sub-system, then the sub-system reports all alarms,
tampering and faults to the master control panel. The master
control panel reacts to particular signals accordingly, and
displays the sub control panel’s address as the source.
After sub control panel enrollment to the master control
panel, these two panels are independent concerning setting
control. Each panel can be operated by its own keypads or
keyfobs. If there is an alarm or fault in the sub control panel, it is
also indicated on the master control panel. In this configuration it
is impossible to control the sub control panel from the master
control panel..
If it is desired to control a sub control panel from a master
control panel (i.e. setting/unsetting), it is possible to enroll a JA-
80 Oasis master control panel to a sub control panel as a
remote control as follows:
1. First enroll the sub control panel to the desired address in the
master control panel by entering 299 on the sub control
panel’s keypad in Service Mode - see 11.2.7 for full details.
2. Switch the master control panel to Service Mode.