background image

Installation manual: Oasis security system JA-80K  

- 8 - 

 MKE51801

 

 

minutes so it is impossible to combine multiple control panels 
in one UC or AC receiver. 

 

 

 

12. Control panel programming 

 

The most convenient way to program the system is to use a 

PC running Comlink software. The system can however also be 
programmed by keying in the sequences in section 12.1.  

 The system should be in Service mode (if not, enter the 

following with the system unset: “

0 Service code” – the  

factory default is 8080)  

 Enter the appropriate programming sequences – see the 

following description (an unfinished sequence can be escaped 
from by pressing the # key),   

 

To exit Service

 

Mode

 press the # key. 

 

12.1. 

Control panel programming sequences  

Function 

Sequence 

Options 

Factory 

default 

Notes 

Entering enrollment mode  

One wireless device (detector, keypad, key fob, siren or sub 

control panel) can be enrolled to each 

address from 01 to 50

.

The system offers vacant addresses one by one, if all 

addresses are occupied no devices can be enrolled. 

A device enrolled to address 01 or 02 disables the 

corresponding hard-wired input 01 or 02.  

In addition to enrollment mode, devices can also be enrolled 

by keying in their production codes (see 12.42). 

Keys:  
up/down arrows

 = address 

scrolling

  

holding 

2

erases the displayed

 

address 

holding 

4

 = 

erases all

 addresses 

#

 = 

exiting

 enrollment mode  

 
 

  

nothing 

 devices enroll by 

connecting their 
power (battery), 
keyfobs also by 
pressing & holding a 
pair of their buttons  

 an occupied address 

is indicated by the A 
indicator being lit 

 enrolling a device to 

a new address will 
move it there 

Exit delay time 

20x 

x

 = 1 to 9 (x10 s =10 to 90 s) 

30s 

Entrance delay time 

21x 

x

 = 1 to 9 (x 5 s = 5 to 45 s) 

20s 

if a final door detector 
is used, then x is 
multiplied by 30s 
instead (i.e. from 30 
to 270s) 

Alarm duration time 

22x 

= 1 to 8 (min.), 9=15min  

4 min. 

0=10s (for testing) 

PGX function 

23x 

 

 

on/off 

(∗

80/

81) 

PGY function 

24x 

x in an unsplit system: 

0 - whole system set (ABC)  = 

PG on 

1 - any system part set = PG on 
2 - AB set (not C) = PG on 
3 - Fire alarm = PG on 
4 - Panic alarm = PG on 
5 - Any alarm = PG on 
6 - AC dropout = PG on 
7 - PG on/off (by 

80 /

81 for 

PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse (keys 

8=X, 

9=Y) 

any 

system 

part set 

x in a split system

 

0 - alarm A = PG on 
1 - alarm B = PG on 
2 - entrance delay A = 
= PG on 
3 - entrance delay B = 
PG on 
4 - A set = X on, B set 
= Y on 
5 - A panic = X on, B 
panic = Y on 
6 - Fire = X on, AC 
dropout = Y on. 
7 - PG on/off (by 

80 

/

81for PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse 
(keys 

8=X, 

9=Y)

 

Enablement of telephone number changes in 
maintenance mode 

25x 

251 = YES      250 = NO 

NO see 

communicator 

Radio interference indication  

26x 

261 = YES      260 = NO 

NO 

30s or longer 

Radio communication supervision 

27x 

271 = YES      270 = NO 

NO  

RESET enabled 

28x 

281 = YES      280 = NO 

YES  

Master control panel enrollment to a sub control 
panel for setting (arming) control 

290 

The sequence triggers 

enrollment. 

(Un)setting the master control 
panel will (un)set the sub control p.
The sub c. panel must be in 
enrollment mode. 

Master code reset 

291 

Returns master code to 1234 

It has no effect on other codes and 
it is recorded in the control panel 
memory 

Measuring signal strength  

298 

Activates measurement 

arrow keys scroll addresses, 
# halts measurement. 

Enrolling the control panel to UC, AC or a sub 
control panel 

299 

The sequence triggers 

enrollment. 

see 12.10  

Setting (arming) without an access code 

30x 

301 = YES      300 = NO 

YES 

by keying: A, B, ABC, 

1, 

2, 

3,

 ∗

Triggered detector indication 

by text on the keypad display

 

31x 

311 = YES      310 = NO 

YES 

allows the display of 
open windows & 
doors,  
to view details press 

?

Confirmation of intruder alarms 

In this mode, the triggering of an intruder detector in a set 
(armed) section will only be recorded to the memory as an 
unconfirmed alarm and if then followed by the activation of any 

32x 

321 = YES      320 = NO

 

 

NO 

An alarm can be 
confirmed by any 
other intruder detector 
in any section which 

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: