Installation manual: Oasis security system JA-80K  

- 12 - 

 MKE51801

 

 

3. In the sub control panel, enter enrollment mode by keying in 

“1” in Service Mode and select the desired address. 

4. In the master control panel enter 290. This way the control 

panel will enroll to the sub control panel to the desired 
address as a remote control.  

5. Switch both control panels to maintenance mode and check 

that all-section setting of the master control panel also sets 
the sub control panel and unsetting the master control panel 
unsets the sub control panel too. Expect approximately 2 
seconds of delay between control panels. 

 

Notes for operating the sub control panel: 

 

The sub control panel can still be operated independently via its 
keyfob or keypad e.g. it can be set while the master control panel is 
unset. If the master control panel changes its status later on, it will 
then control the sub control panel to achieve synchronisation. 

 

To disable the master control panel’s ability to control the sub control 
panel, enter the sub control panel’s enrollment mode, select the 
address where the master control panel is enrolled and erase the 
master control panel from this address by pressing and holding key 2.  

 

12.11. Master 

code 

reset 

If the master code has been forgotten or a card lost, it is 
possible to use the following sequence to reset the master code 
to the factory-default 1234:  

 

291 

 

Note:

 Resetting the master code has no effect on other codes and 

cards. Resets are recorded in the control panel memory and sent to the 
ARC if used (

A

larm 

R

eceiving 

C

entre, previously called a central 

monitoring station). 

 

 

12.12.  Control panel enrollment to UC or AC modules 

or to a sub control panel  

Keying in 

299

 sends an enrollment signal to enroll the control 

panel to UC-82 or AC-82 receiving modules  (see 11.6). This 
sequence can also be used to enroll a sub control panel to a 
master control panel (see 12.10). 

 

 

12.13.  Setting (Arming) without an access code 

 

“Hot” setting keys (short-cut keys for setting) A, B, ABC or 
entering “

 number” can be enabled for use without a valid access 

code or card. If disabled, then hot key use or entering “

 number” 

has to be followed by a valid access code or card to have any 
effect:  

 

Function/sequence 

301 

300 

All-section setting 

ABC key 

Code/card

 

Setting of A 

A key 

A key,  code/card

Setting of AB (or B) 

B key 

B  key, code/card

Event memory recall 

 ∗

4 code/card 

  If you remotely operate the system by mobile phone, you can 

press 

1 for the ABC key, 

2 for key A, and 

3 for key B. 

  Controlling the PG outputs by keying in 

8 or 

9 or pressing 

 

and 

  is unaffected by these settings. These keys can 

however be disabled by a special sequence (see 12.27). 

 

Factory default setting:

 Setting (arming) without an access 

code enabled.  

 

12.14. Triggered-detector 

indication 

Pressing the 

key

 

checks if any detectors are permanently 

triggered, e.g. if any doors or windows are open. The following 
sequence enables the display of text concerning active 
detectors.     

 

3 1 1

 indication 

enabled 

3 1 0

   indication disabled 

 

Factory default setting:

 

indication enabled

 

12.15.  Confirmation of intruder alarms 

To reduce the risk of false alarms and to comply with British 
standard BSI DD243, the control panel allows alarm 
confirmation logic to be enabled as follows:   

 

3 2 1

 confirmation 

logic 

enabled

 

3 2 0

   confirmation logic 

disabled

 

 

Confirmation logic: 

 If the system is set (armed) and any intruder detector gets 

triggered, i.e. a detector with an instant, delayed, or next-
delayed reaction, an alarm will not be caused but the control 
panel will record a so-called unconfirmed alarm. 

  If any other intruder detector is triggered in a set section within 

40 minutes of the above event, an intruder alarm will be 
triggered. If no other detector is triggered during this period, 
the control panel will stop waiting for confirmation. 

 The alarm must be confirmed by another detector than the 

first one, and if the second one is a motion detector its 
detection area must not cover the same area as the first 
detector to be triggered. This must be ensured by the proper 
location of detectors. 

  An unconfirmed alarm is recorded in control panel memory but 

can also be sent to the ARC, or to the user by SMS report. 

  If the first triggered detector has a delayed reaction, it will start 

a so-called unconfirmed entrance delay. This delay is 
indicated the same way as an ordinary entrance delay, but if 
no other delayed detector is triggered during this delay, there 
will be no alarm if the unconfirmed entrance delay is 
exceeded, with another unconfirmed alarm being recorded in 
the control panel memory.  If there is any other delayed or 
next-delayed detector triggered during the entrance delay 
period, it will confirm the entrance delay, and if this delay is 
exceeded (due to no unsetting being done) it will trigger an 
intruder alarm at the end of the delay.  

  If the unconfirmed entrance delay is confirmed by an instant 

detector it will trigger an internal warning alarm immediately 
(e.g. an internal siren) and if the entrance delay times out then 
an external alarm will be triggered. 

  An unconfirmed alarm can be confirmed by any other intruder 

detectors in the system as long as the detectors are assigned 
to a set (armed) section. 

 The confirmation of intruder alarms has no effect on fire, 

panic, 24-hour, tamper, or technical alarms. These alarms are 
triggered immediately without confirmation. 

 

Note:

 When the first detector is triggered it begins a process 

which waits 40 minutes for any possible confirmation of the 
alarm (unconfirmed alarm status) during which the system works 
exactly the same way as if the confirmation function had not 
been enabled. 

    

 

Warning: 

 If intruder alarm confirmation is enabled, it is 

necessary to install enough detectors in the building to detect an 
intruder even if he/she is only moving in one particular place. 

 

Factory default setting:

 confirmation disabled 

 

12.16.  Exit delay beeps 

 

The exit delay can be indicated by beeps from the keypad and 
internal siren. The beeps get faster in the last 5 seconds. 

 

3 3 1

 Beeps 

enabled

 

3 3 0

 Beeps 

disabled

 

 

Factory default setting

Beeps enabled

 
 
 
 
 
 

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: