background image

Installation manual: Oasis security system JA-80K  

- 14 - 

 MKE51801

 

 

Unsetting (disarming) the system with a final door detector 

  If a final-door detector gets triggered in a set (armed) system, 

an entrance delay will begin with a duration of between 30 and 
270 seconds. 

 If a normal delayed detector gets triggered while the user 

enters a building, the system starts an ordinary entrance delay 
of between 5 and 45 seconds.  

 If a final-door detector is triggered first, a longer entrance 

delay will begin. If during this delay an ordinary delayed 
detector is then triggered, the remaining entrance delay will 
then be shortened to the delay associated with detectors of 
this kind. 

 

Note: 

Only use status-reporting detectors such as the JA-80M or JA-

82M, or the hard-wired inputs of wireless keypads, or the hard-wired 
inputs of a control panel as final-door detectors.  This mode is unsuitable 
for pulse detectors such as JA-80P motion detectors, or the hard-wired 
inputs of JA-80E hard-wired keypads which also have a pulse reaction. 

Factory default setting:

 No final-door detectors in the system. 

 

 

12.24.  Partial setting (arming) or system splitting 

 

The control panel can be configured in three ways as follows: 

 

the entire system sets and unsets together or, 

  the system partially sets and unsets to protect only 

certain parts of a house during the day, while people 
are still present in the unset parts or, 

  the system can be split into two independently 

set/unset sections for two separate users and also with 
a common section if desired. 

 
Program as follows to configure the system as desired: 

 

66x 

where x =0  = unsplit system 

(setting/unsetting as an 

entire system)

   

x=1 = partial setting 

(for setting sections A, AB, 

or ABC) 

x=2 = split system 

(sections A and B can be 

set/unset independently by separate users, 
with section C only being automatically set 
when both A and B are manually set) 

 

Notes: 

 

For an unsplit system, 

all intruder detectors are set/unset 

immediately after the user sets/unsets the system. Assigning wireless 
devices, access codes and keyfobs to various sections of the system 
has no effect in this mode. 

 

Partial setting 

is especially suitable

 

for homes and apartments where 

the user wishes to protect different parts of the premises during the 
day. Detectors can be assigned to three sections, A, B and C. Using 
setting (arming) key A on the system keypad, you can set section A, 
e.g. setting the garage area in the afternoon. Using setting key B you 
can set sections A and B simultaneously e.g. in the evening before 
going to sleep  to protect the garage (section A) and the ground floor 
of the house (section B). The ABC total-setting button is used when 
leaving the home to set all sections, A,B and C. If you then use a valid 
access code or card for unsetting (disarming), all sections will be 
unset. The assignment of codes or cards to sections has no effect in 
this mode.   

 

A keyfob can also be used for partial setting control. Buttons 

 and 

 can be programmed to set and unset the entire system, and 

buttons 

+

 can be programmed for setting (arming) sections A 

and AB respectively to partially set the system. (see 12.40 for details 
on partial setting by keyfob). 

 

Split system mode

 is especially suitable where two families (A and 

B) live in a single house or two companies (A and B) share one 
building. The system behaves as two independent systems, one being 
section A and the other, section B. There is also a common section C 
which is only set if section A and section B are set at the same time. 
and is commonly used for shared entrances, doors etc. Detectors can 
be assigned to sections A, B or C. Access codes and cards can be 
assigned to operate either section A or B (not both), or alternatively to 
section C to access the entire building. The same is true for keyfob 
access. 

 

Partial setting only has an effect on intruder detectors, i.e. detectors 
with instant, delayed or next-delayed  reactions. Detectors with fire, 
tamper, panic and 24-hour reactions are always able to trigger their 
kind of alarm immediately, whether their section is set (armed) or not. 

 

Factory default setting

: Unsplit system. 

 

12.25.  Automatic summer time (daylight saving time) 

If enabled, this feature automatically offsets the system time to 
that of summer time, or daylight saving time as it is also known,:   

 

6801

  automatic summer time enabled 

6800

  automatic summer time disabled 

 

Note: 

If automatic summer time is enabled, the control panel’s internal 

clock is automatically offset by +1 hour on March 31

st

 at midnight.  The 

offset is then removed on October 31

st

 at midnight to return to winter 

time. 

 

Factory default setting:

 

automatic summer time disabled

  

 

12.26.  Tamper alarm in response to an increase in 

the number of triggered tamper sensors 

This feature allows permanently triggered tamper sensors to be 
ignored:  

 

6811

  ignore permanently triggered tamper sensors, i.e. 

only react to an increase in the number of triggered 
tamper sensors. 

6810

  react with a tamper alarm to all triggered tamper 

sensors 

 

Note: 

Ignoring permanently triggered tamper sensors is useful for 

example when carrying a detached  wireless keypad around with you 
during installation as this avoids unnecessary tamper indication.  

 

Factory default setting:

 react with a tamper alarm to all 

triggered tamper sensors 

 

12.27.  Operating the PG outputs using 

8 and 

Using this feature the PGX and PGY outputs can be controlled 
from the keypad by pressing the 

8 and 

9 keys (or keys 

 

and

 

).  

 

6821

 control 

enabled 

6820

  control disabled  

 

Notes:  

 

The PG outputs can only be operated from the keypad if they have 
their ON/OFF or pulse functions enabled. 

 

In addition to controlling the PG outputs using keys 

8 and 

9, PG 

outputs can also be controlled by access codes, access cards, 
keyfobs and detector signals (see 12.40 and 12.41 for details). 

 

If a PG output should only be operated by a valid access code or 
card, then control by 

8 and 

9 should be disabled and the codes and 

cards should be programmed to control the PG outputs instead (see 
12.41). 

 

Factory default setting:

 

control enabled

 

 

12.28.  Permanent alarm status display for a set 

system 

The below sequence enables the permanent display of alarm 
status on the keypad unit, even if the system is set.  

 

6831

  permanent status display enabled 

6830

  display time a maximum of 3 minutes if any section is 

set (armed) 

Notes:  

 

European legislation requires status displaying to be suppressed 
within three minutes of setting (arming) the system, no matter how 
much or little of the system is set. This feature can be used to ignore 
this requirement if appropriate. 

 

The wireless keypad can continuously display  the status if powered 
by an external power supply. If powered by internal batteries the 
keypad will turn off its display after 20 seconds of not being used ( in 
Service Mode the display turns off after 15 minutes of no use by the 
installer). 

Содержание Oasis JA-80

Страница 1: ...trol panel installation manual This manual is valid for control panel JA 80K version KE60108 printed on internal circuit board The control panel can be configured by a PC running ComLink software vers...

Страница 2: ...WIRELESS SIREN ALARM ENABLED IW AND EW 13 12 22 AUTO BYPASS USER APPROVAL VIA THE KEY 13 12 23 FINAL DOOR DETECTORS 13 12 24 PARTIAL SETTING ARMING OR SYSTEM SPLITTING 14 12 25 AUTOMATIC SUMMER TIME D...

Страница 3: ...two inputs are not used the two addresses can be used to enroll wireless devices Hard wired inputs are also provided by some wireless devices such as keypads door detectors and PIR movement detectors...

Страница 4: ...e T 200 mA The control panel power supply is double insulated safety class 2 and does not incorporate a protective earth wire A double insulated power cable should be used with a minimum cross section...

Страница 5: ...ered and an external warning will only follow if the entrance delay has been exceeded PGX PGY are a pair of terminals providing programmable outputs If an output is activated it switches to GND with a...

Страница 6: ...r a while before pressing and holding the key the language can be selected for each individual keypad in the system i e different keypads can display different languages for example if foreigners are...

Страница 7: ...siren can be activated by pressing its button A JA 80A outdoor siren can be activated for signal strength measurement by opening its cover thereby triggering its cover tamper switch Each installed dev...

Страница 8: ...min 4 min 0 10s for testing PGX function 23x 7 on off 80 81 PGY function 24x x in an unsplit system 0 whole system set ABC PG on 1 any system part set PG on 2 AB set not C PG on 3 Fire alarm PG on 4 P...

Страница 9: ...O NO Changes internal clock 1h on Apr 1 1h on Nov 1 Tamper signal differential indication Tamper alarm in response to an increase in the number of triggered tamper sensors 681x 6811 ignore permanently...

Страница 10: ...nsplit then ABC hh hours mm minutes No action The scheduled actions will happen every day Changing the service code 5 NC NC NC new code 4 digits 8080 enter NC twice Go to maintenance mode 292 switches...

Страница 11: ...led 2 6 0 disabled Factory default setting disabled Note In some places the system can be permanently or occasionally affected by radio interference e g by nearby radar stations TV transmitters etc In...

Страница 12: ...ors 3 1 1 indication enabled 3 1 0 indication disabled Factory default setting indication enabled 12 15 Confirmation of intruder alarms To reduce the risk of false alarms and to comply with British st...

Страница 13: ...l i e setting by keyfob does not trigger an approval request The automatic bypass of a detector will end after the detector has been de triggered for example if a door is closed If auto bypass user ap...

Страница 14: ...es as two independent systems one being section A and the other section B There is also a common section C which is only set if section A and section B are set at the same time and is commonly used fo...

Страница 15: ...eceive a notification earlier than a year later change the internal clock settings to the day and month you prefer before exiting Service Mode by entering 4hhmmDDMMYY and then re adjust the clock to t...

Страница 16: ...ing the B key on the keypad e g setting arming the garage and the ground floor during the night ABC using the ABC key on the keypad e g to set the entire system when leaving the house In a split syste...

Страница 17: ...n be enrolled instead If a device with production code xx x has already been enrolled to another address in the past and if the device is now enrolled to a new address then it will be moved to the new...

Страница 18: ...the menu and then keypad text After editing keypad text using Comlink software all keypads including wireless ones must be connected to the digital bus to save the changes to the keypad units by clic...

Страница 19: ...ard then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same c...

Страница 20: ...mode as follows 1 The control panel must be in maintenance mode if not then enter 0 master code or card factory default 1234 while the system is totally unset 2 Press key 5 the display indicates Codes...

Страница 21: ...register at www GSMLink cz 15 Basic guidance for installers 1 Create an installation plan that sufficiently covers the building to be protected 2 If the customer requests changes to the suggested conf...

Страница 22: ...d and reports to the control panel Alternatively power the keypad with an AC adaptor to prevent sleep mode or install an indoor wireless siren type JA 80L to generate entrance delay beeps 17 Control p...

Отзывы: