24 Pipework
Check valve mounting
The EHN series is equipped with a check valve for the prevention of a back
flow, siphon and overfeeding. A back pressure valve is attached to the FC type.
In the following cases be sure to install the check valve.
• The suction side liquid level is higher than the discharge side (See the diagram
below). Or an injection point is below the suction side liquid level at atmospheric
pressure.
• The elevation difference between two liquid levels is
fi
ve meters or below,
even if the discharge side liquid level is higher than the suction side.
• Suction side pressure is higher than the discharge side pressure.
• Discharge pressure (including pipe resistance and discharge head) is below
0.13MPa. (0.049MPa for B31 and C36).
Suction side
Discharge side
Suction side
Discharge side
5m or below