DOC. MIE11110 Rev. 5
Page 60 of 110
- N. 1 Cable for low voltage measurement connection, shielded, 4
m long, terminated on one side with the measurement connector,
and on the other side with two 4 mm banana plugs.
- N. 2 Clamps.
C) Input connection, voltage more than 10 V:
- N. 2 measurement cables.
- N. 2 Clamps.
HV cables shall be connected while T 2000 is powered-off. HV
clamps shall have a minimum clearance of 20 mm with respect to
all conductive surfaces, so to avoid discharges during operation.
After connections, the area around the HV clamps shall be
isolated, so that no accidental contact can occur. If something
goes wrong for any reason, power-off T 2000 before getting close
to HV connections.
BEFORE TEST START, MAKE SURE THAT YOU CONNECTED T
2000 HV OUTPUT TO THE PRIMARY AND NOT TO THE
SECONDARY SIDE. IN CASE OF ERROR, YOU WOULD GENERATE
A DESTROYING VOLTAGE AT THE VT PRIMARY!
As the test is to be performed on the 3000 V range, press test
START button (56): the following message will be displayed.
The HV is generated only while the START button (56) is kept
pressed: this is an additional safety feature. The operator will
have both hands occupied: one for the knob (6), the other for the
button (56); however, this is much safer than starting the HV
generation, and then forgetting it in the ON state.
You have to turn ON the HV key (28), and adjust the
VSEC
voltage to the nominal voltage, if it is less then 3000 V, or at 2000
V, by the adjustment knob (6); the screen shows:
. The applied primary voltage;
. The measured secondary voltage;
. The transformer ratio;
. The percentage ratio error with respect to the nominal;
. The polarity, as OK or KO. You will notice that the % error does
not change as a function of the test voltage.
Содержание T2000
Страница 1: ...DATE 18 11 2009 DOC MIE11110 REV 5 T 2000 APPLICATION GUIDE ...
Страница 45: ...DOC MIE11110 Rev 5 Page 45 of 110 ...
Страница 81: ...DOC MIE11110 Rev 5 Page 81 of 110 2 Selection time about 30 ms LTC fails ...
Страница 83: ...DOC MIE11110 Rev 5 Page 83 of 110 4 Same LTC as above fault on this selection ...
Страница 91: ...DOC MIE11110 Rev 5 Page 91 of 110 The connection diagram is the following ...
Страница 102: ...DOC MIE11110 Rev 5 Page 102 of 110 The connection for this test is modified as shown in the following figure ...
Страница 105: ...DOC MIE11110 Rev 5 Page 105 of 110 ...