DOC. MIE11110 Rev. 5
Page 18 of 110
A) Output connection, 800 A:
- N. 2 High current connection cables, 100 sq. mm, 4 m long.
Terminated on one side with the high current connector; on the
other side, it is possible to use one of the following three
connections.
. The male to male jumper, that allows closing the cable loop into
the hole of the current transformer.
. The high current clamp, that eases the connection to the bars,
but has a maximum current rating of 400 A.
Do not go beyond
this value, as the heat can damage the clamp
!
. The high current vice, that is a bit less easy to use than the
clamp, but that allows testing up to the maximum current rating.
However, with tests at 800 A, the burden of the 4 m cables can
impeach to reach this current. If the test current is not the
desired one, use the 1 m connection cables provided.
B) Input connection:
- N. 2 measurement cables, for the secondary current, plus N. 2
Clamps. In alternative, if desired: N. 1 Clip-on transformer, plus N.
2 measurement cables (to the clip-on transformer).
- N. 2 measurement cables (to the 600 V measurement), or N. 1
cable for low voltage measurement connection, shielded, 4 m long
(for the 10 V measurement; shown in the circuit diagram), plus N.
2 Clamps to connect the voltage measurement.
Primary clamps shall be well tightened on a clean surface, so that
contact resistance is negligible.
For secondary connection, it is possible to decide whether to
measure the secondary current by opening the circuit or by means
of the optional clip-on current transformer; to this purpose, the
clip-on transformer is more easily used, but it looses accuracy.
Secondary leads should be twisted to reduce stray flux influence.
Take care of current direction, else the polarity test will give
wrong result: the red socket (output or input) is the positive; with
the clip-on transformer, look at the arrow or at the red mark
(entering current).
Also for the measurement of the voltage you have to take care of
the polarity. You can use either the 10 V metering input or the
Содержание T2000
Страница 1: ...DATE 18 11 2009 DOC MIE11110 REV 5 T 2000 APPLICATION GUIDE ...
Страница 45: ...DOC MIE11110 Rev 5 Page 45 of 110 ...
Страница 81: ...DOC MIE11110 Rev 5 Page 81 of 110 2 Selection time about 30 ms LTC fails ...
Страница 83: ...DOC MIE11110 Rev 5 Page 83 of 110 4 Same LTC as above fault on this selection ...
Страница 91: ...DOC MIE11110 Rev 5 Page 91 of 110 The connection diagram is the following ...
Страница 102: ...DOC MIE11110 Rev 5 Page 102 of 110 The connection for this test is modified as shown in the following figure ...
Страница 105: ...DOC MIE11110 Rev 5 Page 105 of 110 ...