DOC. MIE11110 Rev. 5
Page 95 of 110
. A single-pole cable for the connection from the test set to the
measurement reel, 4 m long, section 2.5 sq. mm.
. A single-pole cable for the connection of the meter to the
reference voltage probe, 50 m long, section 1 sq. mm. Wound on a
wheel.
. One test probe to measure the voltage drop; material: zinc-
plated iron; length: 0.5 m. Complete with connector for the
measurement cable.
Once the connection is performed, press START and slowly
increase the output current, to a value close to the maximum
allowed by the output. The display shows:
. The applied test voltage;
. The injected current;
. The voltage drop between the system earth connection and the
voltage spike;
. The corresponding earth resistance.
Now it is necessary to move the voltage spike, as said before,
until the resistance measurement does not change very much: this
is the earth resistance of the system. Once the result is achieved,
press SAVE and slowly reduce to zero the current.
2.3
S
OIL RESISTIVITY
When this test is selected, the following menu is displayed.
Purpose of the test is to measure resistivity of the soil where the
plant is to be sited, in order to be able to design the earth
connection grid.
Содержание T2000
Страница 1: ...DATE 18 11 2009 DOC MIE11110 REV 5 T 2000 APPLICATION GUIDE ...
Страница 45: ...DOC MIE11110 Rev 5 Page 45 of 110 ...
Страница 81: ...DOC MIE11110 Rev 5 Page 81 of 110 2 Selection time about 30 ms LTC fails ...
Страница 83: ...DOC MIE11110 Rev 5 Page 83 of 110 4 Same LTC as above fault on this selection ...
Страница 91: ...DOC MIE11110 Rev 5 Page 91 of 110 The connection diagram is the following ...
Страница 102: ...DOC MIE11110 Rev 5 Page 102 of 110 The connection for this test is modified as shown in the following figure ...
Страница 105: ...DOC MIE11110 Rev 5 Page 105 of 110 ...