DOC. MIE11110 Rev. 5
Page 100 of 110
LINE LENGTH
(km)
LINE IMPED.
(Ohm)
TEST CURRENT
(A)
10
4
Up to 16
20
8
Up to 8
50
20
Up to 4
100
40
Up to 2
200
80
Up to 1
In the average, the line argument is 80°. The ratio of output
voltage versus output current is 2ZL.
The connection to the line to be tested is performed as shown in
the following figure. For the connection, it is advisable to use the
SU3000 protection module shown in the figure. The procedure is
the following.
- The test is performed on two lines, 1 and 2, that are short-
circuited between them at the other end of the line.
- Open SU3000. Connect one side to ground, and the other side to
two cables: one will go to T 2000, the other to the line to be
tested. Note that until the SU3000 is OPEN, the switch is open,
and there is no ground connection.
- Close SU3000, close the switch: the two cables are connected
to ground. Now you can connect to T 2000 output, and to the line
no. 1, that will be closed to ground.
- Connect line 2 to the other output of T 2000.
- SU3000 can be left closed for added safety, as it does not
influence the current path, PROVIDED THAT THE LINE IS NOT
GROUNDED AT THE FAR END. If lines are grounded at the far end,
the safety device switch should be opened prior to testing.
Содержание T2000
Страница 1: ...DATE 18 11 2009 DOC MIE11110 REV 5 T 2000 APPLICATION GUIDE ...
Страница 45: ...DOC MIE11110 Rev 5 Page 45 of 110 ...
Страница 81: ...DOC MIE11110 Rev 5 Page 81 of 110 2 Selection time about 30 ms LTC fails ...
Страница 83: ...DOC MIE11110 Rev 5 Page 83 of 110 4 Same LTC as above fault on this selection ...
Страница 91: ...DOC MIE11110 Rev 5 Page 91 of 110 The connection diagram is the following ...
Страница 102: ...DOC MIE11110 Rev 5 Page 102 of 110 The connection for this test is modified as shown in the following figure ...
Страница 105: ...DOC MIE11110 Rev 5 Page 105 of 110 ...