DOC. MIE11110 Rev. 5
Page 36 of 110
Keep the test duration as short as possible: if you exceed the
above table, the test set stops automatically the test, and does
not allow to proceed for 3 minutes. If test duration is less than
the above, stop duration is proportionally reduced.
When you are satisfied with the result, press SAVE: test result is
saved. Return to zero the adjustment knob (6), and set the
Interposing module IM2000selector to position 1.
WHEN YOU DISCONNECT THE PRIMARY CABLES, PLEASE
CONSIDER THE TEST DURATION. IF IT WAS LONG,
CONNECTION VICES AND CABLE CAN BE VERY HOT: USE
PROTECTION GLOVES!
1 .1.4. CT tests : burden, secondary side
When this test is selected, the following menu is displayed.
Purpose of the test is to measure the CT burden in terms of VA.
This test is performed applying current to the CT secondary
connections (and not current to the primary side, as in the former
test), and measuring the secondary current and voltage. With this
test, it is possible to apply the nominal current to the burden,
while in the previous test this current can be less or much less,
depending upon the CT nominal primary current.
The connection diagram is the following.
Содержание T2000
Страница 1: ...DATE 18 11 2009 DOC MIE11110 REV 5 T 2000 APPLICATION GUIDE ...
Страница 45: ...DOC MIE11110 Rev 5 Page 45 of 110 ...
Страница 81: ...DOC MIE11110 Rev 5 Page 81 of 110 2 Selection time about 30 ms LTC fails ...
Страница 83: ...DOC MIE11110 Rev 5 Page 83 of 110 4 Same LTC as above fault on this selection ...
Страница 91: ...DOC MIE11110 Rev 5 Page 91 of 110 The connection diagram is the following ...
Страница 102: ...DOC MIE11110 Rev 5 Page 102 of 110 The connection for this test is modified as shown in the following figure ...
Страница 105: ...DOC MIE11110 Rev 5 Page 105 of 110 ...