CHV180 series frequency inverter special for elevator Detailed function description
.79.
Function
Code
Name
Description
Setting
Range
Factory
Setting
PC.08
Current
command
filter
coefficient
0~65536
0~65536
1000
Bit0 and Bit1 are current loop filter parameters. The response of system will be
decreased when they are increased, The parameter usually is adjusted with speed
loop P3.02 and P3.06,If there is abnormal noise when the motor is running, the noise
can be eliminated by increasing the parameter or P3.02 and P3.06.Bit2~bit5 are
reserved.
6.14 Pd Group –Factory Setting
This group is only used for inverter manufacture, please don’t try to open and change
the parameters, otherwise may cause the inverter couldn’t work or damage.