IntesisBox
®
KNX - Daikin A.C. (SKY & VRV line)
User's manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
64 / 66
60
Status_ Mode Text
14 byte DPT_String_8859_1 16.001
R
T ASCII String
Fan Speed
61
Status_ Fan Speed / 2 Speeds
1 byte
DPT_Scaling
5.001
R
T 50% - Speed 1; 100% - Speed 2
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
R
T 33% - Speed 1; 67% - Speed 2; 100% -
Speed 3
Status_ Fan Speed / 2 Speeds
1 byte
DPT_Scaling
5.001
R
T 1 - Speed 1; 2 - Speed 2
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
R
T 1 - Speed 1; 2 - Speed 2; 3 - Speed 3
62
Status_ Fan Speed 1
1 bit
DPT_Bool
1.002
R
T 1 - Speed 1
63
Status_ Fan Speed 2
1 bit
DPT_Bool
1.002
R
T 1 - Speed 2
64
Status_ Fan Speed 3
1 bit
DPT_Bool
1.002
R
T 1 - Speed 3
65
Status_ Fan Speed Text
14 byte DPT_String_8859_1 16.001
R
T ASCII String
Vanes
66
Status_ Vane Up-Down / 5 pos
1 byte
DPT_Scaling
5.001
R
T 20% - Pos1; 40% - Pos2; 60% - Pos3;
80% - Pos4; 100% - Pos5
Status_ Vane Up-Down / 5 pos
1 byte
DPT_Enumerated
5.010
R
T
1 - Pos1; 2 - Pos2; 3 - Pos3;
4 - Pos4; 5 - Pos5
67
Status_ Vane Up-Down Swing
1 bit
DPT_Bool
1.002
R
T 0 - Stop; 1 - Swing
68
Status_ Vane Up-Down Pos1
1 bit
DPT_Bool
1.002
R
T 1 - Position 1
69
Status_ Vane Up-Down Pos2
1 bit
DPT_Bool
1.002
R
T 1 - Position 2
70
Status_ Vane Up-Down Pos3
1 bit
DPT_Bool
1.002
R
T 1 - Position 3
71
Status_ Vane Up-Down Pos4
1 bit
DPT_Bool
1.002
R
T 1 - Position 4
72
Status_ Vane Up-Down Pos5
1 bit
DPT_Bool
1.002
R
T 1 - Position 5
73
Status_ Vane Up-Down Text
14 byte DPT_String_8859_1 16.001
R
T ASCII String
Temperature
74
Status_ AC Setpoint Temp
2 byte
DPT_Value_Temp
9.001
R
T 16ºC to 32ºC