This formula will be applied as soon as the
Control_ Setpoint Temperature
and
Control_ Ambient Temperature
objects are written at least once from the KNX
installation. After that, they are kept always consistent.
Note that this formula will always drive the AC indoor unit demand in the
right
direction, regardless of the operation mode (Heat, Cool or Auto).
It also must be remarked that, if using a Daikin centralized control system for
the supervision/control of multiple indoor units, it will report the actual setpoint
and ambient temperature on the AC indoor units, which may be different than
the ones at the KNX side.
4.7 Scene Configuration dialog
Figure 4.25
Parameter detail
All the parameters in this section are related with the Scene properties and communication
objects. A scene contains values of: On/Off, Mode, Fan speed, Vane position, Setpoint
Temperature and Remote Controller Disablement.
4.7.1 Enable use of scenes
This parameter shows/hides the scene configuration parameters and communication objects.
Figure 4.26
Parameter detail
o
If set to
“no”
the scene parameters and communication objects will not be shown.
o
If set to
“yes”
the scene parameters and communication objects will be shown. To execute
a scene through the byte-type object, a value from
“0”
to
“4”
has to be sent,
correponding each one to a different scene (i.e. “0” = Scene 1;… “4” = Scene 5).