4.1 General dialog
Inside this parameter’s dialog it is possible to activate or change the parameters shown in the
Figure 4.1
.
The first field shows the URL where to download the database (or pr3) and the user manual
for the product.
4.1.1 DK-RC-KNX-1i is master in P1/P2 bus
This parameter changes the gateway’s behavior, being able to program it as master or slave
in P1 P2 bus.
o
If set to “
no
”, the gateway will work as a slave and it will be necessary to have a BRC
remote controller configured as a master.
o
If set to “
yes
” the gateway will be master of the bus. It is not necessary to have any BRC
remote controller in this case but, if there are, they must be configured as slaves. The
next parameter is also shown when selecting DK-RC-KNX-1i as master in P1 P2 bus:
Figure 4.3
Parameter detail
If VRV system, indoor unit is slave of Operating Mode:
VRV indoor units can be configured as master or slave of Operating Mode.
If
configured as slave
=
“yes”
, the unit will take the operating mode of the master
indoor unit in the system (i.e. if master unit is in Heat mode, slaves will be also in
Heat mode).
If
configured as slave
=
“no”,
it means is the master unit, then the unit will take the
operating mode selected through the BRC or DK-RC-KNX-1i, and the other slave indoor
units will adopt this operating mode.
Important:
Only ONE indoor unit can be configured as master of operating mode. If
more than one indoor unit is configured as master, the system will not work properly
.
There are some compatible Operation Modes that slave indoor units can use while the
master indoor unit is operating in another one:
MASTER INDOOR UNIT
SLAVE INDOOR UNIT(s)
Heat
Heat, Fan