background image

IntesisBox

® 

KNX - Daikin A.C. (SKY & VRV line) 

User's manual r1.0 eng 

 
 

 

 

© Intesis Software S.L. - All rights reserved 

This information is subject to change without notice

 

 

IntesisBox

®

 

is a registered trademark of Intesis Software SL

 

 

URL 
Email 
tel 

  http://www.intesis.com                                          

[email protected] 
+34 938047134 

5 / 66 

 

 

4.7.1

 

Enable use of scenes ............................................................................. 37

 

4.7.2

 

Scenes can be stored from KNX bus ........................................................ 38

 

4.7.3

 

Enable use of bit objects for scene execution ............................................ 39

 

4.7.4

 

Scene “x” preset ................................................................................... 39

 

4.8

 

Switch-Off Timeouts Configuration dialog ....................................................... 41

 

4.8.1

 

Enable use of Open Window / Switch off timeout function .......................... 41

 

4.8.2

 

Enable use of Occupancy function ........................................................... 42

 

4.8.3

 

Enable use of SLEEP timeout .................................................................. 45

 

4.9

 

Binary Input “x” Configuration dialog ............................................................. 46

 

4.9.1

 

Enable use of Input “x” .......................................................................... 46

 

4.9.2

 

Contact type ......................................................................................... 46

 

4.9.3

 

Debounce time ..................................................................................... 46

 

4.9.4

 

Disabling function.................................................................................. 47

 

4.9.5

 

Function ............................................................................................... 47

 

5.

 

Specifications ................................................................................................. 55

 

6.

 

AC Unit Types compatibility. ............................................................................ 56

 

7.

 

Error Codes ................................................................................................... 57

 

Appendix A – Communication Objects Table ................................................................ 60

 

 

Содержание DK-RC-KNX-1i

Страница 1: ...IntesisBox DK RC KNX 1i v2 0 User s Manual Issue Date 25 02 2016 r1 0 eng...

Страница 2: ...ument is furnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced sto...

Страница 3: ...ice IntesisBox is a registered trademark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 3 66 Gateway for integration of Daikin air conditioners into KNX TP 1 E...

Страница 4: ...atus 17 4 2 7 Enable use of Text object for Mode 18 4 2 8 Enable use of Legacy_ object for Mode 18 4 3 Special Modes Configuration dialog 18 4 3 1 Enable use of POWER mode 19 4 3 2 Enable use of ECONO...

Страница 5: ...bus 38 4 7 3 Enable use of bit objects for scene execution 39 4 7 4 Scene x preset 39 4 8 Switch Off Timeouts Configuration dialog 41 4 8 1 Enable use of Open Window Switch off timeout function 41 4 8...

Страница 6: ...odes available Power Economy Additional Heating and Additional Cooling Timeout for Open Window and Occupancy Sleep function also available Control of the AC unit based in the ambient temperature read...

Страница 7: ...e If we want to use the RC as slave its PCB switch must be set at S position and the DK RC KNX 1i must be configured as master Check compatible Daikin remote controllers in the link provided in sectio...

Страница 8: ...38047134 8 66 Connections diagrams DK RC KNX 1i without DAIKIN RC DK RC KNX 1i with DAIKIN RC Figure 2 2 Connections diagrams Max 500 m P1 P2 Connection to P1 P2 bus Two wires cable KNX TP 1 EIB bus P...

Страница 9: ...d setup This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS ETS database for this device can be downloaded from http www intesis com down eib DK RC KNX...

Страница 10: ...first time the gateway shows the following default parameter configuration Figure 4 1 Default parameter configuration With this configuration it s possible to send On Off Control_ On Off change the A...

Страница 11: ...ry to have any BRC remote controller in this case but if there are they must be configured as slaves The next parameter is also shown when selecting DK RC KNX 1i as master in P1 P2 bus Figure 4 3 Para...

Страница 12: ...th the response when received Figure 4 4 Parameter detail Delay before sending READs sec With this parameter a delay can be configured between 0 and 30 seconds for the READs sent by the Control_ objec...

Страница 13: ...happens Important If an initial scene is enabled and it has as Value for Remote Lock unchanged or unlocked this would unlock the remote controller because the initial scene has priority over the Contr...

Страница 14: ...different from the existing one Important If the stored value is 0 hours the gateway will not send the status to KNX 4 1 7 Enable object Error Code 2byte This parameter shows hides the Status_ Error...

Страница 15: ...ue and Dry mode with a 14 value 4 2 1 When mode is AUTO Status_ objs report actual operating status This parameter shows the real status of the indoor unit when Auto mode is enabled o If set to no whe...

Страница 16: ...rcentage demand is meant to be applied on a fluid valve of the heating cooling system DK RC KNX 1i device does not provide individual control on the internal parts of the indoor unit as can be its com...

Страница 17: ...ill appear Figure 4 8 Parameter detail DPT type for Mode Object This parameter lets choose between the datapoints 0 Up 1 Down DPT_1 008 and 0 Decrease 1 Increase DPT_1 007 for the Control_ Mode object...

Страница 18: ...the object will not be shown o If set to yes the Status_ Mode Text object will appear Also in the parameters will be shown five text fields one for each mode that will let modify the text string disp...

Страница 19: ...a value concerning On Off Mode Fan Speed or Setpoint Temperature is received from KNX while any Special Mode is running 1 the Special Mode will stop and the previous state will be recovered The value...

Страница 20: ...Number of degrees Celsius that will increase in Heat Mode or decrease in Cool Mode while in Power Mode Fan Speed for this mode Fan Speed that will be set in the unit while in Power Mode 4 3 2 Enable...

Страница 21: ...et to yes the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode objects and new parameters will appear When a 1 value is sent to the Control_ communication object Additional Heating...

Страница 22: ...r When a 1 value is sent to the Control_ communication object Additional Cooling Mode will be enabled and the Status_ object will return this value When a 0 value is sent to the Control_ communication...

Страница 23: ...are available in the indoor unit 2 or 3 speeds available Figure 4 13 Parameter detail Changing the fan speeds will also change the fan speed byte type object and the bit type objects erasing all the g...

Страница 24: ...last one sending a 3 The Status_ object will always return the value for the fan speed selected Important In both cases if a 0 value is sent to the Control_ object the minimum fan speed will be select...

Страница 25: ...value between 84 and 100 is sent to the Control_ object the third speed will be selected The Status_ object will return a 33 when the first speed is selected a 67 for the second one and a 100 for the...

Страница 26: ...lower limit This parameter lets choose if roll over will be enabled yes or disabled no for the Control_ Fan Speed object 4 4 4 Enable use of bit type Fan Speed objects for Control This parameter show...

Страница 27: ...es the Status_ Fan Speed Text communication object o If set to no the object will not be shown o If set to yes the Status_ Fan Speed Text object will appear Also in the parameters will be shown two or...

Страница 28: ...ies and communication objects 4 5 1 Indoor unit has Up Down Vanes This parameter lets you choose if the unit has Up Down Vanes available or not Figure 4 17 Parameter detail o If set to no all the para...

Страница 29: ...ype for Vane Up Down With this parameter is possible to change de DPT for the Control_ Vane Up Down and Status_ Vane Up Down byte type communication objects Datapoints Scaling DPT_5 001 and Enumerated...

Страница 30: ...irst vane position a 40 for the second one a 60 for the third one an 80 for the fourth one and a 100 for the fifth and last one 4 5 4 Enable use of obj for Vane Up Down This parameter shows hides the...

Страница 31: ...wn object 4 5 5 Enable use of bit type Vane U D objects for Control This parameter shows hides the bit type Control_ Vane Up Down objects o If set to no the objects will not be shown o If set to yes t...

Страница 32: ...the Status_ Vane Up Down Text object will appear Also in the parameters will be shown six text fields five for the Vane Position and one for the Swing function that will let modify the text string dis...

Страница 33: ...nication objects 4 6 1 Periodic sending of Status_ AC Setp This parameter lets you change the interval of time in seconds from 0 to 255 at the end of which the AC setpoint temperature is sent to the K...

Страница 34: ...rameter will only be available for the only cylically and cyclically and on change options and lets you change the interval of time in seconds from 1 to 255 at the end of which the AC return temperatu...

Страница 35: ...oint temperature Important If a setpoint temperature above the upper defined limit or below the lower defined limit is sent through the Control_ Setpoint Temperature object it will be ALWAYS applied t...

Страница 36: ...s requires programming the AC indoor unit to work as explained in option 1 above As in this case the AC return temperature could be different as of the KNX ambient temperature the DK RC KNX 1i applies...

Страница 37: ...or the supervision control of multiple indoor units it will report the actual setpoint and ambient temperature on the AC indoor units which may be different than the ones at the KNX side 4 7 Scene Con...

Страница 38: ...communication objects will not be shown o If set to yes the communication objects and a new parameter will appear To store a scene through the byte type object a value from 128 to 132 has to be sent t...

Страница 39: ...o If set to yes the communication objects will appear To execute a scene by using these objects a 1 value has to be sent to the scene s object we want to execute i e to execute scene 4 a 1 has to be...

Страница 40: ...ne x Value for Vane Up Down This parameter lets you choose the vane position of the indoor unit when the scene is executed The following options are available POSITION 1 POSITION 2 POSITION 3 POSITION...

Страница 41: ...Enable use of Open Window Switch off timeout function This parameter shows hides the Control_ Switch Off Timeout communication object which lets you Start Stop a timeout to switch off the indoor unit...

Страница 42: ...These commands will be used in the next parameter if set to yes Reload last On Off val once window is closed If set to no once the switch off timeout is stopped any value will be reloaded If set to y...

Страница 43: ...eat mode or increasing the setpoint when in Cool mode Also new parameters will appear Figure 4 34 Parameter detail Temp delta decrease HEAT or increase COOL C This parameter lets configure the delta t...

Страница 44: ...new parameters will appear Temp delta decrease HEAT or increase COOL C This parameter lets configure the delta temperature that will be applied when the timeout is extinguished Important When there i...

Страница 45: ...out period no action will be performed 4 8 3 Enable use of SLEEP timeout This parameter shows hides the Control_ Start Sleep Timeout communication object which lets you start a timeout to automaticall...

Страница 46: ...binary inputs properties and communication objects 4 9 1 Enable use of Input x This parameter enables the use of the Input x and shows hides the Status_ Inx communication object s which will act as co...

Страница 47: ...2 1 True Disable 0 False Enable is selected the input can be disabled using the value 1 and enabled using the value 0 4 9 5 Function This parameter lets choose the function that will have the binary i...

Страница 48: ...am will be sent Value on rising edge This parameter lets select the value that the Binary Input x will send on a rising edge contact activated When On is selected the binary input will always send tel...

Страница 49: ...e below When Always is selected the binary input will send any value cyclically Also a new parameter will appear see below When Never is selected cyclical sending will be disabled Period for cyclical...

Страница 50: ...n On increase is selected the binary input will always send telegrams with a 1 value for a short operation and an increase step for a long operation When Off decrease is selected the binary input will...

Страница 51: ...or the cyclical sending of a long operation o When Shutter Blind is selected the communication objects and new parameters for the Input x will appear as shown below Figure 4 44 Parameter detail Send t...

Страница 52: ...thod for the shutter blind When Step Move Step is selected On a rising edge contact activated a step stop telegram will be sent and will begin a time called T1 If a falling edge occurs contact deactiv...

Страница 53: ...s parameter lets select if the Binary Input x will send a telegram or not after a bus recovery and the type of telegram sent if enabled When No action is selected no telegram will be sent after a bus...

Страница 54: ...efined in the next parameter on a rising edge contact activated Figure 4 49 Parameter detail Scene when contact is activated This parameter lets choose the scene that will be activated on a rising edg...

Страница 55: ...38047134 55 66 5 Specifications Dimensions 70 X 70 X 28 mm Weight 70 g KNX current consumption 5 mA P1 P2 Bus current consumption 45 mA Operating Temperature 25 85 C Stock Temperature 40 85 C Isolatio...

Страница 56: ...notice IntesisBox is a registered trademark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 56 66 6 AC Unit Types compatibility A list of Daikin indoor unit mo...

Страница 57: ...ensor error 48 CF High pressure switch sensor 49 E0 Outdoor Unit Protection devices activated 50 E1 Outdoor uni9t PCB assembly failure 52 E3 High pressure switch HPS activated 53 E4 Low pressure switc...

Страница 58: ...phase Open phase 147 U2 Power voltage failure Instantaneous power failure 148 U3 Failure to carry out check operation transmission error 149 U4 Communication error between indoor unit and outdoor uni...

Страница 59: ...ature sensor error 262 35 Outdoor air temperature sensor error 263 36 Remote controller temperature sensor error 267 3A Water leakage sensor 1 error 268 3H Water leakage sensor 2 error 269 3C Dew cond...

Страница 60: ...0 W T 0 Cool 1 Heat 3 Control_ Mode Cool On 1 byte DPT_Scaling 5 001 W T 0 Off 0 1 100 On Cool 4 Control_ Mode Heat On 1 byte DPT_Scaling 5 001 W T 0 Off 0 1 100 On Heat 5 Control_ Mode Auto 1 bit DPT...

Страница 61: ...ne Up Down 5 pos 1 byte DPT_Scaling 5 001 W T 0 29 Pos1 30 49 Pos2 50 69 Pos3 70 89 Pos4 90 100 Pos5 Control_ Vane Up Down 5 pos 1 byte DPT_Enumerated 5 010 W T 1 Pos1 2 Pos2 3 Pos3 4 Pos4 5 Pos5 17 C...

Страница 62: ...30 Control_ Lock Remote Control 1 bit DPT_Bool 1 002 W T 0 Unlocked 1 Locked 31 Control_ Lock Control Objects 1 bit DPT_Bool 1 002 W T 0 Unlocked 1 Locked Special Modes 32 Control_ Power Mode 1 bit D...

Страница 63: ...ntrol_ Disable Input 2 1 bit DPT_Bool 1 002 W T 0 Enable 1 Disable Control_ Disable Input 2 1 bit DPT_Enable 1 003 W T 0 Disable 1 Enable 49 Control_ Disable Input 3 1 bit DPT_Bool 1 002 W T 0 Enable...

Страница 64: ...63 Status_ Fan Speed 2 1 bit DPT_Bool 1 002 R T 1 Speed 2 64 Status_ Fan Speed 3 1 bit DPT_Bool 1 002 R T 1 Speed 3 65 Status_ Fan Speed Text 14 byte DPT_String_8859_1 16 001 R T ASCII String Vanes 66...

Страница 65: ...des 81 Status_ Power Mode 1 bit DPT_Switch 1 001 R T 0 Off 1 On 82 Status_ Econo Mode 1 bit DPT_Switch 1 001 R T 0 Off 1 On 83 Status_ Additional Heat 1 bit DPT_Switch 1 001 R T 0 Off 1 On 84 Status_...

Страница 66: ...demark of Intesis Software SL URL Email tel http www intesis com info intesis com 34 938047134 66 66 95 97 Status_ Inx Value 2 byte DPT_Value_2_Count 8 001 R T Status_ Inx Value 2 byte DPT_Value_Temp...

Отзывы: