3.
Enter the desired Forced Door Output time. For
example:
45 # ttt # 0 # **
where, ttt=forced door time, to nearest 10’s
seconds, entered as 10-990; default=30 seconds.
4.
Press * to exit Program mode.
4.4 Programming
Keypad Options
and Parameters
4.4.1 User Lockout
Option
The prox.pad plus unit supports two types of user
lockouts: “Lockout By Location” and “Lockout By
Group.” The two lockouts share the following features:
(1) entering Program mode always clears an active
lockout (2) and neither the “master,” the“ supervisor,”
nor an “emergency” user can be locked out. The user
lockout function, which is enabled by default, can be
disabled through Command 30 option #5. The lockout
type is selected through Command 30 option #8 and
defaults to “Lockout By Location.”
4.4.1.A Lockout By Location
In the Lockout By Location mode, the location of the
Lockout Code in the user table determines which users
are locked out. Entering a Lockout Code (when no
lockouts are active) excludes all users programmed in
locations greater than the location of that Lockout
Code. For example, if user #20 is programmed as a
Lockout Code and that user’s PIN is entered, then
users #21 and above are locked out.
Entering the same Lockout Code cancels the current
lockout. If a different Lockout Code (programmed in
a location less than the current lockout) is entered
during an active lockout, the lockout is “lowered” to
the location of that PIN. This means that to cancel a
4.4 Programming Keypad Options and Parameters
Chapter 4: Programming
prox.pad plus Install/Program. Manual, PPP, D2
4-19