Chapter 3: Wiring
Chapter 3 provides wiring diagrams and associated
procedures.
3.1 Wiring the
prox.pad plus Unit
Select one of these three wiring options, Alarm Shunt,
Forced Door, or Propped Door, depending on how
the prox.pad plus unit’s AUX relay is to be employed
for this installation (refer to Chapter 4 for program-
ming information). Then refer to sections 3.1.1- 3.1.3
as appropriate.
3.1.1 Wiring the AUX
Relay for Use as
Alarm Shunt
The Alarm Shunt Relay function may be necessary
when a separate existing security system is in place.
The Alarm Shunt Relay keeps an alarm panel zone
from going into alarm when the door is opened, after
a valid code is entered. The Alarm Shunt function is
assigned to the Aux relay by default. To incorporate
this feature, follow the steps below; see Figure 3-1.
3.1.1.A Wiring the Alarm Shunt Relay
1.
Turn OFF power to the prox.pad plus unit, and
then unlatch the keypad from the plastic housing.
2.
Locate connector P2 (the 6-pin connector) on the
main circuit board and plug on the 6-pin harness.
(The 2-pin jumper on pins 5 and 6 of connector
P2 must be removed first.)
3.
Connect the 6-conductor harness to connector P2
as shown in Figure 2-1.
4.
Connect the blue wire to the “Common” side of
the door contact.
5.
Connect the green wire to the “Normally Open”
side of the door contact.
6.
Make a parallel connection to the green and blue
wires and run the leads to the alarm panel.
NOTE:
This feature requires that you use the “Door Con-
tact” input as shown in Figure 3-1.
prox.pad plus Install/Program. Manual, PPP, D2
3-1