Monitor output 
voltage (1) 

Alignment outdoor (2)  Alignment indoor (3) 

60-250 mV 

Poor. Re-adjust (4) 

Good 

less than 60 mV 

Poor. Re-adjust (4) 

Note: 

Table shows voltage under non-attenuation sheet condition. 

Testing the unit: 

Test monthly. Walk in front of the receiver 

and see if the Alarm LED lights when the beam is blocked. 
Confirm the relay function by observing the status light on the 
control panel. 

Maintaining the unit: 

The units are virtually maintenance free 

except for units located in dusty or dirty locations. Clean dirty 
units with a damp cloth as necessary. 

Adjusting the response time 

See Figure 15. 

Response time (sec.). 1. Response 0.05 sec: running at full 
speed. 2. Response 0.3 sec: walking quickly; 3. Response 0.7 
sec: walking. 

This feature is used to modify the response time of the beam to 
best suit the application. The unit cannot detect objects that 
move faster than the set response time. However, increasing 
the set response time may result in the unit not detecting 
people. 

Changing beam frequency 

Change the beam frequency to prevent cross talk or bypass of 
beams. This can occur with line or 2-stacked protection. 

Figure 16: 

Setting the beam channel. 

1.  Set the transmitter and receiver to the same channel. The 

units do not provide protection if set to different channels. 

2.  See figure 16 to set the beam channel when installing two 

or more units in a line or 2-stacked protection. 

A: 

Line 

protection; 

B: 

2-stacked protection; 

C. 

Line and 2-stacked 

protection. 

Note: 

When multi-stacked or line protection is used, it is 

recommended that beam alignment is done with a tester to 
improve reliability as well using the beam frequency change-
over function. When multi-stacked protection is used, both 
upper and lower sensors should have the same model 
numbers. 

External dimensions 

See Figure 17. 

Figure 17 description 

Knockout 

Wire lead 

Troubleshooting 

 

Problem 

Possible cause 

Remedy 

Operation 
LED does 
not light. 

No power supply. 

Turn on the power. 

Bad wiring connection or 
broken wire (short). 

Check and correct the wiring. 

Problem 

Possible cause 

Remedy 

Alarm LED 
does not 
light when 
the beam is 
interrupted. 

No power supply. 

Turn on the power. 

Poor wiring connection or 
broken wire (short). 

Check and correct the 
wiring. 

Beam is reflected on to 
another object and sent 
to the receiver. 

Remove the reflecting 
object or change the beam 
direction. 

Two beams are not 
broken simultaneously. 

Interrupt two beams 
simultaneously. 

The beam interruption 
time is shorter than the 
set response time. 

Adjust the beam response 
time. 

Alarm LED 
continues 
to light. 

Beam alignment is out. 

Check and adjust again. 

Shading object between 
the transmitter and the 
receiver. 

Remove the shading 
objects. 

Unit optics are dirty. 

Clean the optics with a soft 
cloth. 

Frequency channel is not 
compatible between the 
transmitter and the 
receiver. 

Readjust to the same 
channel. 

Intermittent 
alarms 

Bad wiring connection. 

Check again. 

Change of supply 
voltage. 

Stabilize supply voltage. 

Shading object between 
transmitter and the 
receiver. 

Remove the shading object. 

A large electrical noise 
source, such as a power 
machine, is located near 
the transmitter and the 
receiver. 

Change location of the 
installation. 

Unstable installation of 
transmitter and receiver. 

Stabilize. 

Dirty transmitter or 
receiver optics. 

Clean the optics with a soft 
cloth. 

Incorrect alignment. 

Check and adjust again. 

Small animals may be 
passing through the two 
beams. 

Increase the response time. 
(impossible in a location 
where the intruder can run 
at full speed.) 

 

Specifications 

 

Model 

PB501 

PB511 

PB521 

Detection 
system 

Simultaneous interruption of 2 beams 

 

Infrared beam  LED pulsed beam, double modulation 

Protection 
distance 

Outdoor 

20 m 

Indoor 

40 m 

Outdoor 

40 m 

Indoor 

80 m 

Outdoor 

60 m 

Indoor 

120 m 

Response 
time 

0.05-0.7 seconds variable (variable at pot) 

Power supply  12-30 VDC (non polarity) 

Current 
consumption 

55 mA or less

75 mA or less 

80 mA or less 

Содержание PB501

Страница 1: ...2013 UTC Fire Security Americas Corporation Inc All rights reserved 1 26 P N 1077838 REV D ISS 19MAR19 PB501 PB511 PB521 Photoelectric Beam Sensor Installation Sheet EN DE ES FR IT NL SV 1 2 4 5 A B C 3 ...

Страница 2: ...stance m Wire size PB501 PB511 PB521 12 V 24 V 12 V 24 V 12 V 24 V AWG22 Ø 0 65mm 210 1900 160 1400 150 1300 AWG20 Ø 0 88mm 360 3200 260 2400 250 2200 AWG18 Ø 1 0mm 540 4900 400 3600 370 3300 AWG17 Ø 1 1mm 650 5900 480 4300 450 4000 10 11 PB50 PA PB50 PA ...

Страница 3: ...P N 1077838 REV D ISS 19MAR19 3 26 12 13 14 15 ...

Страница 4: ...errupted eg by an insect or a leaf it does not initiate an alarm Four beam frequency channels are available to prevent cross talk when using multiple units Part description Figure 1 The product is supplied with the following items Please check that they are all included 1 Terminals 2 Beam channel 3 Lens 4 View finder 5 Operation LED 6 Horizontal adjustment 7 Vertical adjustment screw 8 Cover 9 Mou...

Страница 5: ...outs Pull the wire through as shown and attach it to the mounting plate Installing a pole mounted system with the PB50 PA pole attachment figure 10 Insert two oval countersunk head screws M4x20 in a pole bracket 1 Fix the pole mounting plate to the pole with the bracket Remove the cover from the unit and detach the mounting plate Insert two M4x10 screws in the pole mounting plate 2 and fix the sen...

Страница 6: ...ut 2 Wire lead Troubleshooting Problem Possible cause Remedy Operation LED does not light No power supply Turn on the power Bad wiring connection or broken wire short Check and correct the wiring Problem Possible cause Remedy Alarm LED does not light when the beam is interrupted No power supply Turn on the power Poor wiring connection or broken wire short Check and correct the wiring Beam is refle...

Страница 7: ...this device is in compliance with the applicable requirements and provisions of the Directive 2014 30 EU and or 2014 35 EU For more information see www utcfireandsecurity com or www interlogix com 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the...

Страница 8: ...riebsbereitschaft und bringen Sie die Abdeckung wieder an Eine Versiegelung des wasserdichten Geräts ist nicht erforderlich Entfernen Sie bei Verlegung des Kabels auf einer Oberfläche die Ausstanzungen auf der Geräterückseite A Kabelführung von oben B Kabelführung von unten C Ausstanzungen Ziehen Sie das Kabel wie gezeigt hindurch und befestigen Sie es auf der Montageplatte Mastmontage des Systems...

Страница 9: ...ndung desselben Kanals fest Sind die Geräte auf unterschiedliche Kanäle eingestellt bieten sie keinen Schutz 2 Hinweise zum Festlegen des Lichtschrankenkanals bei Installation von zwei oder mehr Geräten hintereinander oder übereinander finden Sie in Abbildung 16 A Hintereinander B Übereinander C Hinter und übereinander Hinweis Bei Positionierung über und hintereinander wird die Verwendung eines Pr...

Страница 10: ...nrot Rechtliche Hinweise Hersteller INVERKEHRBRINGER UTC Fire Security Americas Corporation Inc 3211 Progress Drive Lincolnton NC 28092 USA BEVOLLMÄCHTIGTER EU REPRÄSENDANT UTC Fire Security B V Kelvinstraat 7 6003 DH Weert Niederlande Produktwarnungen und Haftungs ausschluss DIESE PRODUKTE SIND FÜR DEN VERKAUF AN UND DIE INSTALLATION DURCH QUALIFIZIERTES PERSONAL VORGESEHEN UTC FIRE SECURITY ÜBER...

Страница 11: ...tación m Nota La maxima distancia de cableado cuando se conectan dos ó mas elementos es el valor mostrado dividido por el numero de elementos Nota La linea de señal se puede cablear hasta 1000 m aproximadamente con cable telefonico AWG22 0 65 mm de diametro Instalación del sistema Instalación de una unidad montada sobre una pared figura 12 Retire la cubierta de la unidad 1 y quite la placa de mont...

Страница 12: ...unidades ubicadas en lugares sucios o con polvo Pase un trapo húmedo por las unidades sucias cuando sea necesario Ajuste del tiempo de respuesta Consulte la figura 15 Tiempo de respuesta seg 1 Respuesta 0 05 seg corriendo a toda velocidad 2 Respuesta 0 3 seg caminando rápidamente 3 Respuesta 0 7 seg caminando Esta función se utiliza para modificar el tiempo de respuesta del haz para adaptarse a la...

Страница 13: ...80 mA o menos Salida de alarma Formulario de salida de relé de contacto sin corriente C Acción de contacto tiempo de interrupción tiempo de retardo 1 3 s Capacidad de contacto 30 V CA CC 0 5 A o menos Modelo PB501 PB511 PB521 Salida de tamper Relé de contacto sin corriente 1b N C Acción activado cuando la tapa del receptor no está colocada Capacidad de contacto 30 V CA CC 0 5 mA o menos LED de ala...

Страница 14: ...s d obstacles penser aux changements de saison Éviter la lumière vive Éviter les éclaboussures Éviter les terrains meubles Figure 3 Distance de protection à l intérieur et l extérieur entre l émetteur et le récepteur Modèle À l extérieur m À l intérieur m PB501 20 40 PB511 40 80 PB521 60 120 Éviter le câblage aérien Pour les installations à l intérieur utiliser les mêmes procédures que pour téléph...

Страница 15: ...l intérieur 3 voir le tableau Procéder à un nouveau réglage si les mesures sont faibles 4 Tension 1 Alignement l extérieur 2 Alignement l intérieur 3 700 mV Optimale Optimale 250 700 mV Bonne Tension 1 Alignement l extérieur 2 Alignement l intérieur 3 60 250 mV Faible Nouveau réglage nécessaire 4 Bonne 60 mV Faible Nouveau réglage nécessaire 4 Remarque Le tableau mentionne des tensions sans utilis...

Страница 16: ...maux dans les deux faisceaux Augmenter le temps de réponse impossible dans les endroits où les intrus peuvent se déplacer en courant très vite Caractéristiques techniques Modèle PB501 PB511 PB521 Système de détection Interruption simultanée de 2 faisceaux Faisceau infrarouge Faisceau pulsé à diodes double modulation Distance de protection À l extérieur 20 m À l intérieur 40 m À l extérieur 40 m À ...

Страница 17: ...pleto dei seguenti elementi Verificare che siano tutti presenti 1 Morsettiera 2 Canale fascio 3 Obiettivo 4 Mirino 5 LED funzionamento 6 Regolazione orizzontale 7 Vite di regolazione verticale 8 Dispositivo di blocco 9 Piastra di montaggio 10 LED allarme 11 LED attenuazione 12 Regolazione tempo di risposta 13 Jack monitor 14 Vite autofilettante 15 Piastra per montaggio su palo 16 Staffa per palo 1...

Страница 18: ...izione figura 14 1 Tester da 3 10 V CC 2 Foglio di attenuazione 3 LED allarme 4 LED attenuazione Continuare con la regolazione fine dell unità finché il LED di attenuazione del ricevitore si spegne Se l unità viene utilizzata all aperto posizionare un foglio di attenuazione sull ottica del ricevitore e continuare con la procedura di regolazione fine finché il LED del ricevitore si spegne Durante l...

Страница 19: ...ente Una importante fonte di disturbo elettrico ad esempio un generatore è vicina a trasmettitore e ricevitore Cambiare la posizione dell installazione Installazione instabile di trasmettitore e ricevitore Stabilizzare Ottiche sporche di trasmettitore e ricevitore Pulire le ottiche con un panno morbido Problema Possibile causa Rimedio Allineamento non corretto Controllare e regolare di nuovo Picco...

Страница 20: ...r Rx Ze zijn ontworpen voor de modus AND gated Een alarm wordt alleen geactiveerd wanneer twee beams gelijktijdig worden onderbroken Indien slechts één beam wordt onderbroken bijv door een insect of een blaadje wordt er geen alarm geactiveerd Er zijn vier beam frequentiekanalen beschikbaar om te voorkomen dat de signalen van meerdere units elkaar beïnvloeden Beschrijving onderdeel Afbeelding 1 Het...

Страница 21: ...de ontvanger plaats de zoeker tussen de twee lenzen en kijk er doorheen Lijn de lenzen horizontal en verticaal uit zodat de unit aan de andere kant zichtbaar is Afbeelding 14 Fijnafstemming van de unit Beschrijving afbeelding 14 1 Tester 3 10 VDC 2 Afzwakkingsvel 3 Alarm LED 4 Auto gain LED Zet de fijnafstemming voort totdat de auto gain LED van de ontvanger uitgaat Als de unit buiten wordt gebrui...

Страница 22: ...etzelfde kanaal Onder broken alarmen Slechte staat van de bedrading Controleer opnieuw Gewijzigde voedingsspanning Zorg voor een stabiele voedingsspanning Afschermend object tussen zender en ontvanger Verwijder het afschermende object Probleem Mogelijke oorzaak Oplossing Een omvangrijke elektrische storingsbron zoals een elektrisch apparaat in de buurt van de zender en ontvanger Wijzig de locatie ...

Страница 23: ...olgende website www recyclethis info Contactgegevens Raadpleeg onze website voor contactgegevens www utcfireandsecurity com SV Installationsanvisningar Produktbeskrivning Fotoelektroniska linjedetektorer PB501 PB511 samt PB521 består av en infraröd sändare och mottagare De är konstruerade att ge larm när de 2 synkroniserade strålarna bryts samtidigt Ett larm avges ej om t ex insekter fåglar eller ...

Страница 24: ...ns lins genom att använda spegelsiktet sitter mellan de 2 linserna Titta in i hålet som utgör spegelsiktet och ställ in sändaren så att du ser mottagaren i siktet gör likadant på mottagarsidan Bild 14 Finjustering Bild 14 beskrivning 1 Testjacksingång för mätinstrument 2 Filter 3 Lysdiod larm 4 Lysdiod dålig signal Finjustera tills mottagarens lysdiod märkt sensitivity attenuation är släckt Vid ut...

Страница 25: ...ken med en mjuk trasa Linsinställningen är dålig Kontrollera och justera linsinställningen Felsymptom Möjlig orsak Atgärd Djur kanske passerar de båda strålarna Ställ längre reaktionstid tänk dock på att man då kanske kan springa snabbt igenom kontrollera Tekniska data Typ PB501 PB511 PB521 Delektions princip Samtidig brytning av 2 strålar IR stråle Dubbelt modulerad pulsad lysdiod Bevaknings räck...

Страница 26: ...ör Directive 2014 30 EU och eller 2014 35 EU För mer information www utcfireandsecurity com eller www interlogix com 2012 19 EU WEEE Produkter märkta med denna symbol får inte kastas i allmänna sophanteringssytem inom den europeiska unionen För korrekt återvinning av utrustningen skall den returneras din lokala återförsäljare vid köp av liknande ny utrustning eller lämnas till en därför avsedd dep...

Отзывы: