Appendix 2 Common EMC Problems and Solutions
‑
154
‑
Figure 6‑2 I/O signal cables with capacitance increased
6.4
RS485&CAN Communication Interference
Take the measures listed in the following table to suppress interference.
No.
Measure
1
Install a 120 Ω termination resistor on each end of the bus.
2
Replace with multi‑conductor shielded twisted pair cables and ground both ends
of the shield.
3
Separate communication cables from power cables with a distance of at least 30
cm.
4
Adopt daisy chain mode for multi‑node communication layout.
5
Add an equipotential bonding grounding cable between nodes during multi‑node
communication (see
6
Install ferrite clamps on both sides of the communication cable or wind the
magnetic ring by one or two turns (see
).
7
Install the magnetic ring on the output side (UVW) of the servo drive by two to four
turns (see
8
Use shielded power cables and ground the shield properly.
Содержание SV660P Series
Страница 1: ...SV660P Series Servo Drive Hardware Guide Data code 19011391 A00...
Страница 55: ...Installation 54 Figure 2 21 Installing the ferrite clamp...
Страница 66: ...Wiring 65 3 3 2 Wiring Diagram for Torque Control Mode Figure 3 5 Wiring in the torque control mode...
Страница 111: ...Wiring 110 Open collector mode For use of the internal 24 V power supply of the servo drive...
Страница 113: ...Wiring 112 Scheme 2 Using the external resistor...
Страница 135: ...Wiring 134 Selecting the regenerative resistor Figure 3 48 Flowchart for selecting the regenerative resistor...
Страница 144: ...Maintenance 143...